0 wiring connections, Iring, Onnections – Emerson Series 610 User Manual

Page 28: Warning, Caution

Advertising
background image

Wiring Connections

24

8.0

W

IRING

C

ONNECTIONS

!

WARNING

Verify that all incoming high and low voltage power circuits are de-energized and locked out

before installing cables or making electrical connections.
All power connections must be completed by a licensed electrician experienced in wiring UPS

equipment and in accordance with all applicable national and local electrical codes.
Improper wiring may cause damage to the UPS or injury to personnel.

!

CAUTION

All shielded cables, non-shielded cables, non-shielded control wires, non-shielded battery

breaker control wires and non-shielded remote control wires must be housed in individual,

separate, steel conduits. Placing multiple cables in the same conduit with other control or

power wiring may cause system failure.

NOTE
Use appropriately sized wire as a grounding conductor. Solid metal conduit is not a suitable

ground conductor for UPS systems and could negatively affect system performance.