Wiring Inspection

26

9.0

W

IRING

I

NSPECTION

1. Verify all power connections are tightened per the torque specifications in Table 3.
2. Verify all control wire terminations are tight.
3. Verify all power wires and connections have proper spacing between exposed surfaces, phase-to-

phase and phase-to-ground.

4. Verify that all control wires are run in steel conduit, separate from all power wiring.

Use 75°C copper wire. Select wire size based on the ampacities in Table 5 of this manual, a reprint of

Table 310-16 and associated notes of the National Electrical Code (NFPA 70).
Use commercially available solderless lugs for the wire size required for your application. Refer to

Table 3. Connect wire to the lug using tools and procedures specified by the lug manufacturer.

Table 2

Power wiring terminals - factory supplied

UPS Module Rating

Connection Type

1000/1100kVA

Busbars for connecting hardware (with 3/8” holes on 1.75” centers) are provided for bypass

input, critical load output and DC wiring terminations. DC busbars for 1000/1100kVA

modules are designed for top or bottom entry and are located adjacent to the input circuit

breaker. Rectifier input wiring is top or bottom entry, directly to busbars on top of the input

circuit breaker. UPS module output wiring (and bypass input for Single-Module Systems) is

top or bottom entry, directly to busbars above the circuit breakers (left side of unit). Field-

supplied lugs are required for all input and output terminations.

Table 3

Torque specifications

NUT AND BOLT COMBINATIONS

Bolt Shaft Size

Grade 2 Standard

Electrical Connections

with Belleville Washers

Lb-in

N-m

Lb-in

N-m

1/4

53

6.0

46

5.2

5/16

107

12

60

6.8

3/8

192

22

95

11

1/2

428

22

256

29

CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING)

Wire Size or Range

Lb-in

N-m

#6 - #4

100

11

#3 - #1

125

14

1/0 - 2/0

150

17

3/0 - 200 MCM

200

23

250 - 400 MCM

250

28

500 - 700 MCM

300

34

CIRCUIT BREAKERS WITH COMPRESSION LUGS (FOR POWER WIRING)

Current Rating

Lb-in

N-m

400 - 1200 Amps

300.00

34.00

TERMINAL BLOCK COMPRESSION LUGS (FOR CONTROL WIRING)

AWG Wire Size or Range

Lb-in

N-m

#22 -#14

3.5 to 5.3

0.4 to 0.6

NOTE: Use the values in this table unless the equipment is labeled with a different torque value.