EMI WLHA User Manual

Page 10

Advertising
background image

www.enviromaster.com

WLCA/WLHA High Wall Evaporator

10

rEfriGErAnt pipinG

The WLCA/WLHA is equipped with a

Flo-Rater/Piston Expansion device. Con-

nections are sweat type.

The suction line (large) must be insulated

the entire length with closed cell, foam tube
insulation. Do not insulate the liquid line

(small). Connect the outdoor unit according

to the instructions supplied with unit.

All horizontal piping runs must be level and

without dips to trap the oil.

pipinG do’s And don’ts

• Avoid piping on a rainy day.

• Use refrigerant grade copper tubing.

• Use a tubing bender and avoid unnec-

essary bending.

• Cap ends of lines until ready for final

connections.

Once the unit is mounted and level

the WLCA/WLHA piping connections can

be made by removing the left end cap and

bottom panel:

1. Remove the Philips-head

screws on bottom of

unit and lift bottom

panel off.

2. Exposed piping and condensate drain

connections. (S

ee table on page 36 for

connection size per unit capacity.)

s

uction line

Liquid line

c

ondensate drain

When matching a the WLHA24 with an
18,000 Btuh condenser circuit, the inter-

connecting suction line needs to be 5/8”
O.D. to match the condenser service valve

connection. Therefore the 3/4” O.D. suc-

tion connection of the WLHA24 unit needs

to be reduced to 5/8” at the WLHA24 unit
connection.

note:

The left end cap must

be removed prior to remov-

ing the bottom. follow the

instructions on page 6 for

removing the end cap.

WLCA/WLHA HiGH WALL EVAporAtor instALLAtion instrUCtions