WLCA/WLHA High Wall Evaporator

between room temperature and setpoint

temperature is less than two degrees. At

that time the electric heat will switch off

and the heat pump (compressor) will take

over the heating demand. The electric
heater will not re-start until a three minute

delay has elapsed. Once the room tem-

perature is satisfied and the two-minute

minimum run time has elapsed, the com-

pressor will cycle off. The compressor will

not re-start until a three minute delay has

elapsed. The fan will operate as described

in “Fan Operation”.

dry mode

For dry mode operation the unit must

have an electric heater. Also the control

must first be configured properly (Heat

source – “ON”). See: Configuration Inter-

face mode.

Dry mode will remove humidity from

the air while maintaining a specific setpoint

temperature. This is done by energizing the

compressor in cooling along with the electric

heater. Dry mode will not maintain a specific

humidity level. The unit must be equipped

with an optional electric heat element.

For Dry Mode operation, first turn the

unit on via the ON/OFF button. Select Dry

mode via the MODE button. The room

temperature and setpoint temperature will

be displayed. Press either the Up or Down

arrow buttons to change the setpoint tem-

perature. The setpoint temperature will

change by one degree with each succes-

sive press of the Up or Down arrow but-

tons. Holding the button in will change the

temperature rapidly.

Place the setpoint temperature at a

desired room temperature. Depending on

the difference between room temperature

and setpoint temperature the compressor

and/or heat source will energize. If the

room temperature and setpoint tempera-

ture are the same the compressor will op-

erate in cooling and the electric heat will

also energize.

Should the room temperature fall be-

low the setpoint temperature by two de-

grees, the compressor will stop and heating

will continue to boost the room temperature

back up to setpoint temperature. If the room

temperature rises above the setpoint tem-

perature by two degrees, heating will stop

and cooling will continue to bring the room

temperature back down to setpoint temper-

ature. The fan will operate continuously at

low speed while in Dry Mode.

In order to prevent short cycling there

is a two minute minimum on time for both

cooling and heating. The minimum off time

is 3 minutes. Also there is a 30 second de-

lay between the start of the compressor

and the start of the heat source.

Auto Changeover mode

For Auto Changeover mode (ACO)

the unit must have a heat source. Also the

control must first be configured properly

(Heat source – “ON”). See: Configuration

Interface mode.

Auto Changeover mode will operate

either Cooling mode or Heating mode.

The control will select the mode of opera-

tion depending on the setpoint tempera-

ture, room temperature and the differen-

tial setting selected in the Configuration

mode (See Configuration mode).

For Auto Changeover mode, first turn

the unit on via the ON/OFF button. Select

Auto mode via the Mode button. The room

temperature and setpoint temperature will

be displayed. Press either the Up or Down

arrow buttons to change the setpoint tem-

perature. The setpoint temperature will

change by one degree with each succes-

sive press of the Up or Down arrow but-

tons. Holding the button in will change the

temperature rapidly.

Place the setpoint temperature be-

low the room temperature by the dead

band amount selected in the configura-

tion mode. The compressor will start and

the unit will run cooling operation as de-

scribed under “Cool Mode”.

If the set point temperature is above

the room temperature by the dead band

amount selected in the configuration

mode, the unit will run heating operation

as described under “Heat Mode”

set time mode

The “TIME” button is used to enter
or exit the Set Time mode. The Set Time
mode can be entered while the control is in

sEqUEnCE of opErAtion – Unit moUntEd KEy pAd modE