to prevent freeze up from occurring. If

freeze up does occur then check the

following.

• Check that the freeze sensor located

in the lowest part of the coil. Generally

this is where freeze up will begin.

• Check that the freeze sensor inserted

fully and snug in the coil fin. If not

another location may need to be

selected. Be careful not to insert the

sensor directly into the coil tube rather
insert the sensor between two tubes.

• Check the indoor air filter. It should

be clean and free of dirt. A dirty filter

will reduce airflow and efficiency.

Also check that the coil is clean.

If the coil is dirty then it should be

cleaned using an appropriate coil

cleaner or mild detergent.

frequently Asked questions

Continued

• Is the equipment being operated

in cooling mode when outdoor

temperatures are below 60°F? If it
is, then the condenser should be

fitted with low ambient control so

that the proper system pressures
are maintained.

• Does the system have the proper

refrigerant charge? A system low

on refrigerant can cause evaporator

freeze-up. To check system charge

you will need to contact a qualified

refrigeration service technician.

Refrigerant charge information can

be found in IOM for the outdoor

condensing unit.