EMI WLHA User Manual

Page 13

Advertising
background image

www.enviromaster.com

13

WLCA/WLHA High Wall Evaporator

rEfriGErAnt proCEssinG

WLCA/WLHA HiGH WALL EVAporAtor instALLAtion instrUCtions

s2CA rEfriGErAnt CHArGE tABLE

Condenser

Evaporator pairing

Line Chg/ft

factory Charge

S2CA99

WLHA09

.25 oz.

28 oz./ 28 oz.

S2CA22

WLHA12

.25 oz.

33 oz./ 33 oz.

S2CA92

WLHA09+WLHA12

.25 oz.

28 oz./ 33 oz.

s1CA rEfriGErAnt CHArGE tABLE

Condenser

Evaporator pairing

Line Chg/ft

factory Charge

S1CA9

WLHA09

.25 oz.

37 oz.

S1CA2

WLHA12

.25 oz.

40 oz.

S1CA8

WLHA24

.56 oz.

51 oz.

S1CA4

WLHA24

.56 oz.

65 oz.

S1CA3

WLCA30

.56 oz.

72 oz.

S1CA6

WLCA36

.56 oz.

90 oz.

s1HA (HEAt pUmp) rEfriGErAnt CHArGE tABLE

Condenser

Evaporator pairing

Line Chg/ft

factory Charge

S1HA9

WLHA09

.25 oz.

41 oz.

S1HA2

WLHA12

.25 oz.

44 oz.

S1HA8

WLHA24

.56 oz.

53 oz.

S1HA4

WLHA24

.56 oz.

67 oz.

8. Charge to proper weight, charge

based on your feet of interconnect
(see below).

Note:

Charging should be done with a

dial-a-charge or weighed in with a scale.

Refrigerant

R-22

refer to refrigerant

Charge table for

specified line charge.

Top discharge
condeser shown

top disCHArGE rEfriGErAnt CHArGE CHArt

Circuit Capacity

Line Chg/ft

factory Charge

ref.

09

.25 oz.

28 oz.

R-22

12

.25 oz.

30 oz.

R-22

18

.56 oz.

48 oz.

R-22

24

.56 oz.

60 oz.

R-22

IMPORTANT NOTES:

I. To find the charge adjustment and system charge for any evaporator and tubing length:

Line Adjustment = (Line Chg/Ft) x Line Length

System Total = Factory Charge + Line Adjustment

2. Round to the nearest ounce and allow for gauges and hoses.

3. Use R22 refrigerant.

Advertising
This manual is related to the following products: