EMI WLHA User Manual

Page 33

Advertising
background image

www.enviromaster.com

33

WLCA/WLHA High Wall Evaporator

q:

The system has just been installed us-

ing an EMI indoor unit and a non-EMI

condenser. There is no display and the

unit will not operate.

A:

EMI air handlers are manufactured with

a low

Volt transformer installed. When

connecting an EMI evaporator to a non-

EMI condenser, check to ensure that
there is no 24

V control transformer in

the outdoor unit. Only one transformer

is required. If both the indoor unit and

outdoor unit contain a transformer, one

must be removed from the system.

q:

The condenser will not start although

the indoor unit appears normal. What
should I do?

A:

At the indoor unit, make sure that the

control is in cooling and the setpoint

temperature is below room temperature.

Next, using a volt meter, check for 24V

across the yellow (Y) and brown (C)

wires. If 24V is present then check for

wiring breaks or improper connections
between the indoor and outdoor units.

A:

Some EMI condensers are equipped

with a manual reset high-pressure

switch. It is located on the high side of

the refrigerant system usually on the

discharge line of the compressor. To

reset, simply push the red button in. If

the switch was tripped there will be a

“click” when it resets.

A:

If the unit is equipped with a condensate

pump check to see if the safety float

has been tripped. This can be done by

first disconnecting both ends of the float

switch. Then with an Ohmmeter, check

for continuity across the switch. If the

switch is open then the pump is not

clearing or the switch may be bad.

troUBLEsHootinG proCEdUrE

Continued

frequently Asked questions

q:

The display on the indoor unit is blank.

What should I do?

A:

Check the power supply (see “Power

supply check” Section). If the unit still

fails to turn on via the On/off button

then inspect the control box for any

apparent wires that may have come

loose during shipping. Also inspect the

circuit boards for burnt components. If

no obvious problem can be found then

replace all circuit boards including the

unit keypad. Do not attempt to trouble
shoot the individual circuit boards.

q:

The display tends to flicker at times. Is

this normal?

A:

A small amount of flickering of the dis-

play is normal. Depending on the room

lighting, flickering may be noticeable at
some times more than others.

q:

How long will the fan run?

A:

While the unit is in cooling or heating

and auto fan mode is selected, Fan

speed will be determined by the micro-

processor and speed adjustment will be

made according to room and setpoint

temperatures. The fan will switch to
High

speed when room temperature

deviates by more than two degrees

from setpoint. The fan will switch to Low

speed if the deviation is one degree.

When the room temperature reaches

setpoint temperature the heat/cool call

is dropped. The fan will then stay on for

an additional 60 seconds to purge unit

of any residual energy. If High or Low

is selected then the fan will operate

continuous regardless of set point or

room temperatures.

q:

What causes my indoor unit to freeze-up?

A:

Evaporator freeze up is usually the

symptom of another problem. Units with

infrared compatible, unit mounted con-

trols are equipped with freeze protection

Advertising
This manual is related to the following products: