www.enviromaster.com

31

WLCA/WLHA High Wall Evaporator

troUBLEsHootinG proCEdUrE

Continued

While in test mode, all timers are

eliminated. Avoid short cycling the

compressor. After system checks

are complete, the control must be re-

turned to normal operation. DO NOT
LEAVE THE SYSTEM IN TEST
MODE!

LoW VoLt ControLs

Cooling only Units

Cooling only units utilize low Volt

interconnecting wires between the indoor

unit, outdoor units and thermostat. For air
handlers with unit mounted controls, wires

(WLCA/WLHA) designated “Y” (yellow) and

“C” (brown) of the indoor air handler should

be connected to the corresponding “Y”

(yellow) and “C” (brown) wires or terminals

of the outdoor condenser. Other wires or

terminals such as “R”(red) or “O” (orange)

may not be needed and should be protect

by a wire nut from making contact with the

junction box or other metal surfaces.

Refer to low Volt interconnect diagram

interconnect diagram Figure 1 for unit
mounted controls and Figure 2

for remote

thermostat connection.

A 24V transformer located in the indoor

air handler unit provides low Volt control

power to both the indoor air handler and
outdoor condenser. The 24

V power supply

can be measured by placing a meter across

the “R” and “C” low Volt terminals of the
air handler. The air handler will switch on

and off the condenser through the yellow

(Y) wire. When the air handler is calling for

cooling, 24V can be measured between
terminals (wires) Y and C.

Electric Heat

Units with electric heat utilize a control

relay located on the circuit board in the

control box. As a safety feature, an auto

resetting limit switch located on the heater

end plate or on the heater assembly will

interrupt power to the heater should an
over-heat condition occur. Each electric

heat assembly is also equipped with a one

time fuse link (if trigered a new fuse link is

required). Should electric heat temperatures

rise above the auto resetting limit switch, a

non-resetting, one time fuse link will open

and the heater will remain off.

The following current values apply

when the unit is connected to a 230V power

supply. These values include fan motor cur-

rent. If the supply power is different, this will

in turn affect the amp draw of the heater.

5kW = 22.3 amps, 4kW = 18 amps,

3kW = 13.5 amps.

optional Heat pump

with Electric Heat

Heat pump units with electric heat utilize

four to six interconnecting, low Volt wires

depending control setup and/or thermostat

selected. Refer to the low Volt interconnect
section and Figures 1 & 2

for your particular

unit.

A 24V transformer located in the indoor

air handler provides low Volt control power
to both the air handler and condenser. With

high Volt power supplied to the condenser,
24

V can be measured across the red (R)

and brown (C) wires at all times.

Cooling:

The air handler will cycle

the condenser on and off through the

yellow (Y) wire. To check for a condenser

signal, select cooling mode on the indoor

unit or thermostat and place the set-point

temperature below room temperature.

Then, with a voltmeter check for 24 Volts

across the yellow (Y) and brown (C) wires.

If no signal is found then re-check all wiring

connections to ensure that they match the

low Volt interconnect diagram. Check the

output of the 24V transformer (located in
the air handler) to ensure that the control

voltage is present.

!

!