troUBLEsHootinG proCEdUrE

Continued

power supply Check

When trouble shooting any EMI prod-

uct, it is important to first check the rating

plate for proper field voltage and breaker

size. Secondly using a voltmeter check the

incoming power supply to see that it agrees

with the rating plate. The incoming power

should not exceed the nameplate voltage.

Also, the incoming power should not be

below the minimum voltage stated on the

rating plate (197V for units rated 208/230V

and 104V for units rated 115V).

A check for low voltage power should

also be made. By placing a voltmeter
across low

Volt terminals “R” and “C” at

the indoor unit, there should be a reading

of 24V.

Figure 1B

Not used

Figure 2 C

Figure 2 A

Figure 2 B

Test Mode

is available for unit mounted

control configuration only. Use of test mode

can aid in the functional check of the unit.

It can also be a helpful tool when trouble

shooting to solve a problem.

To enter test mode, while the unit is in

off mode, press “On/Off”, “PROG” AND

“Time” buttons simultaneously for three

seconds. To exit press again or remove

power to the unit. While in test mode all
timers are shortened.