9

GENERAL INSTALLATION

1. Verify that the 30A input circuit breaker on the GXT5000R-208 is in the OFF position.
2. For GXT5VBATTW120 only - Connect the 208V, one-foot-long cord, from the rear of the

GXT5000R-208 to the mating external battery connector on the rear of the

GXT5VBATTW120.

3. Connect the L6-20P from the load to the L6-20R on the rear of the GXT5000R-208. Turn

on the 20A circuit breaker on the rear of the GXT5000R-208.

4. Verify that the EPO connector and jumper are in place.
5. Connect any 120V loads to the 5-15R receptacles on the rear of the GXT5VBATTW120, if

used. Verify that the 4A circuit protector is not tripped.

6. Connect the DC cable from the GXT5000R-208 to the first battery cabinet. If additional

battery cabinets are used, connect each battery cabinet to the next using the 18-inch

battery cable supplied with each additional cabinet.

7. Connect the input cord to the nearest L6-30 branch circuit receptacle.
The UPS is now ready to turn on. Power will be applied to the load (bypass mode) immediately

whenever the input 30A circuit breaker is initially closed. Please refer to the Operating

Instructions section of this manual before turning on the input circuit breaker.