OPERATING INSTRUCTIONS

Turn On

Once the AC supply has been applied to the unit, power will be applied to the load (bypass

mode) immediately when the 30 A input circuit breaker is initially closed. Turn the unit ON

(inverter mode) by pressing the ON button once.

Manual Bypass

To manually put the unit in Bypass mode, press the Standby button

once. Pressing this

button once will cause the load to be transferred to bypass power. Pressing this button a sec-

ond time will result in loss of power to the output receptacles and connected loads.

Standby

To put the unit in Standby mode, press the Standby button

while the unit is in bypass

mode.

!

CAUTION
Pressing the Standby/Manual Bypass button during normal

operation while the inverter is on will transfer the load to bypass

power, if the bypass voltage and frequency are within a safe

range.
The bypass power path does NOT protect the connected

equipment from disturbances on the utility supply.

!

CAUTION
Pressing the Standby/Manual Bypass button when the UPS is in bypass

mode will shut off power to the output receptacles and connected loads.

Turning the unit off leaves the UPS in standby mode. To fully isolate the

load from power, open the input circuit breaker.