Troubleshooting, Table 2 led indicators, Roubleshooting – Emerson LIEBERT GXT5000R-208 User Manual

Page 26: Table 2, Led indicators

Advertising
background image

22

TROUBLESHOOTING

This section presents various problems a user might encounter. Use this information to deter-

mine whether external factors cause the problem and how to remedy the situation.
1. The Fault LED will illuminate, indicating the UPS detected a problem.
2. An alarm will sound, alerting that the UPS requires attention.
3. One or more additional load/battery level LED indicators will be illuminated to provide a

diagnostic aid to the operator, as shown below:

4. Record the LED condition and horn condition. Turn off the 30A AC input circuit breaker

on the rear of the UPS and restart the UPS based on the Operating Instructions in this

manual.

If a problem persists, consult your local dealer, Liebert representative or the Liebert World-

wide Support Group—telephone numbers may be found on the back of this manual. Please

have the UPS model number and serial number available at the time of your inquiry.

Table 2

LED indicators

LED status

Diagnosis

Audible alarm

All LEDs on

AC input overvoltage

Continuous beep

A, F on

On bypass due to overtemperature condition until the UPS

cools, then re-transferring load to inverter.

Continuous beep

Or off due to very high temperatures.

D, F on

Battery overvoltage

Continuous beep

E, F on

Battery mode overload

Half-second beep

every 1 second

A, D, F on

Inverter output short

Continuous beep

Line LED

flashing

Input AC present, but exceeds PFC input requirements

(> 276 or < 170)

All battery

capacity LEDs

flashing

Battery failure warning

Continuous beep

B, C, F on

EPO shutdown

Continuous beep

Other

Record condition of LEDs and horn. Contact Liebert technical

support.

Fault

LED

F

A B C D E