OPTIONAL BATTERIES - PROGRAMMABLE RUN TIME

The GXT5000R-208 may be equipped with up to five battery GXT5VBATT cabinets. At least

one battery cabinet is required. The first battery cabinet may be a GXT5VBATTW120 if a

120V, 400VA auxiliary voltage source is needed.
The enhanced communication provides an estimated run time in minutes, taking into account

the number of battery cabinets and UPS load. The number of attached battery cabinets must

be programmed into the UPS for accurate time estimates.
Even when external monitoring software is not used, the enhanced accuracy is applied to the

low battery contact closure alarm provided by the standard relay alarm card.
The front control panel provides a convenient method of programming the number of battery

cabinets.

Programming the GXT5000R-208 for Battery Cabinet Count

Programming the UPS uses the ON button,

the Standby button, and the Load LEDs on

the front control panel (see illustration at

right).
The battery count display mode should be

entered only with the UPS load off.
Once the battery count is displayed, the user

has the option of leaving the battery count

unchanged or modifying the count to match

the number of attached battery cabinets.
The count should always be checked on new

installations to confirm the setting.
In this mode, the Load LEDs function as Bat-

tery Count LEDs. On completion of the pro-

cedure, one to five Load LEDs illuminate to

indicate how many battery cabinets are con-

nected to the GXT5000R-208 (see illustration

below).

On
e B
a

tt

er

y

Tw

o Batteries

Fo
ur Ba

tte
rie
s

Five Batteries

T

h

ree Batter

ies

One Battery Connected

Two Batteries Connected

Three Batteries Connected

Four Batteries Connected

Five Batteries Connected