Major components, Rectifier/power factor correction (pfc) circuit, Inverter – Emerson LIEBERT GXT5000R-208 User Manual

Page 9: Battery charger, Dc to dc converter, Battery, Ajor, Omponents

Advertising
background image

5

MAJOR COMPONENTS

Transient Voltage Surge Suppression (TVSS) & EMI/RFI Filters

These UPS components provide surge protection and filter both electromagnetic interference

(EMI) and radio frequency interference (RFI). They minimize any surges or interference

present in the utility line and keep sensitive equipment protected.

Rectifier/Power Factor Correction (PFC) Circuit

In normal operation, the rectifier/PFC circuit converts utility AC power to regulated DC

power for use by the inverter while ensuring that the waveshape of the input current used by

the UPS is near ideal. Extracting this sinewave input current achieves two objectives: the

utility power is used as efficiently as possible by the UPS, and the amount of distortion

reflected on the utility is reduced. This results in cleaner power being available to other

devices in the building not being protected by the GXT5000R-208.

Inverter

In normal operation, the inverter utilizes the DC output of the power factor correction circuit

and “inverts” it into precise, regulated sinewave AC power. When utility power fails, the

inverter takes power from the battery through the DC to DC converter and inverts it into

alternating current. In both modes of operation, the UPS inverter is on-line and continuously

generating clean, precise, regulated AC output power.

Battery Charger

The battery charger utilizes utility power and precisely regulates it to continuously “float”

charge the battery system.

DC to DC Converter

The DC to DC converter utilizes energy from the battery system and raises the DC voltage to

the optimum operating voltage for the inverter. This allows the inverter to operate continu-

ously at its optimum efficiency and voltage, thus increasing reliability.

Battery

The GXT5VBATT and GXT5VBATTW120 employs valve-regulated, nonspillable, lead acid

batteries. At an ambient temperature of 68°F to 77°F (20°C to 25°C) and with the UPS float

charging, the battery design life will be maintained.