Table 3 troubleshooting guide, Table 3, Troubleshooting guide – Emerson LIEBERT GXT5000R-208 User Manual

Page 27

Advertising
background image

23

Table 3

Troubleshooting guide

Fault

classification

LED

display

Audible

alarm

Condition

Response

time

Bus

fault

C & F

LEDs

Continuous

± Bus V > 450 VDC

80 ms

± Bus V > 410 VDC

1.5 seconds

± Bus V < 230 VDC

80 ms

|(Abnormal + Bus V)-(|-Bus V |)| > 40 VDC or

|(+Bus V)-(Abnormal |-Bus V|)| > 35 VDC

2 minutes

Inverter

fault

B & F

LEDs

Continuous

Inverter output power > 276 VAC or

Inverter output power < 140 VAC

Minimum

90 ms

Inverter output power short. UPS short circuit

fault.

5 cycles

Overtemp

fault

A & F

LEDs

Continuous

If temperature is > 90°F (32°C) detected

NTC’s temperature on CNTL pcb.

5 seconds

If temperature > 65°F (18°C) and < 90°F

(32°C), then transfer to bypass mode, and

wait until temperature < 40°F (5°C) then back

to inverter mode

4.5 seconds

Battery

overvoltage fault

D & F

LEDs

Continuous

Battery voltage > 15V per unit

6.4 seconds

Battery mode

overload alarm

E & F

LEDs

0.5 second

beep, recurring

every 1 second

Battery mode load > 105%, < 125%

1 minute

Battery mode load > 125%, < 150%

10 seconds

Battery mode load > 150%

Instantaneous

Bypass

fault

A, B & F

LEDs

Continuous

Try to turn unit on (inverter mode). Check

output load for shorts.

Instantaneous

Relay bonded

on N.O.

A, C & F

LEDs

Continuous

Check inverter output voltage, before inverter

soft start. If detected inverter output voltage

> 85 VAC, then set fault.

Instantaneous

Inverter mode

output power

short circuit

fault

A, D & F

LEDs

Continuous

If detected inverter output power I > 70 ADC

and output voltage < 90 VDC, then increase

{short_cnt}.

If {short_cnt} > 30 any time in period of

96 ms, then set UPS short circuit fault.

Not specified

Line LED

flash warning

Line voltage > 276 VAC

48 ms

Line voltage < 170 VAC

160 ms or

(48 ms)

Battery

disconnected

warning

BAT LED

flashing

0.5 second

beep, recurring

every 1 second

When UPS turn off charger and detected

battery voltage < 10 VDC per unit

Instantaneous

Battery fail

warning

BAT LED

flashing

Continuous

When the UPS is in battery test sequence

and detected battery voltage < 10 VDC per

unit

Instantaneous

Bypass mode

bus overvoltage

or input voltage

too high fault

All LEDs bright,

buzzer beeping

Continuous

Bus overvoltage > 400 VDC or

input voltage > 292 VAC

Not specified

Input voltage

> 292 VAC

All LEDs bright,

buzzer beeping

Continuous

Check input voltage—must be greater than

292 VAC.

Not specified

BUS voltage

fault

All LEDs bright,

buzzer beeping

Continuous

Check the BUS voltage—must be lower than

242 VDC.

Not specified