Initial installation – Enviro DV36 User Manual

Page 18

Advertising
background image

Initial Installation

QUALIFIED INSTALLERS ONLY

18

����

�������

Figure 25: Wire Spacers.

it to the inner wall frame using four (4) 11⁄2” wood screws. If a wall is

greater than 8” (203mm) in depth, the clearance above the flex must be

43⁄8” (111mm)

6. Apply a bead of Mill-Pac Black sealant to the new Ø4” (10 cm) by 5” (12.5

cm) provided flue collar adaptor. Press the flue collar into the flue outlet of

the fireplace so that the Mill-Pac seals the flue collar to the flue outlet.

7. Stretch both the Ø4” (10 cm) flex vent and the Ø65⁄8” (16.25 cm) flex intake

liner to the length needed to ensure the flex can be easily connected to the

Figure 26: Wire Spacer in Place.

vent terminal.

8. Slide the Ø65⁄8” (16.25 cm) flex intake liner

over the flex vent. Install four (4) wire

spacers around the flex pipe. Ensure the

wire spacers are positioned at either end of

the pipes, and at each end of any elbows in

the liners (refer to Figure 25 and 26).

9. Install the flex pipe assembly through

the wall thimble, ensure that this portion

of pipe slides through the outside wall

far enough to connect onto the vent

termination cap.

KIT COMPONENTS:

Qnty

Description

Qnty

Description

1

Horizontal direct vent termination cap

4

Wire spacers

1

Flue collar adapter

1

4 oz tube Mill-Pac Sealant

1

Wall thimble

1

4 oz tube RTV silicone

1

5’ (190 cm) length of Ø4” (10 cm) double walled flex pipe

12

9/16” tech screws

1

5’ (190 cm) length of Ø65⁄8” (16.8 cm) double walled flex pipe

8

11⁄2” wood screws

Please ensure that all components are supplied with this kit. If components are missing or have

been damaged, contact your dealer, distributor, or courier company. Do not attempt the installation if

components are missing or damaged.

INSTALLATION INSTRUCTIONS:
1. Plan your installation and clearances to combustibles. Decide on a location for the unit that will meet

the clearances noted in the venting section, and any or all local code requirements.

2. Set the appliance in the desired location. Determine if any wall studs, electrical wiring, or plumbing

pipes are in the way of the venting system as it passes through the exterior wall. The fireplace location

should be adjusted if obstructions are found in the wall.

3. Project a line from the center point of the flue outlet upward and outward to the desired flue outlet

location on the exterior wall. Using this center point, scribe a 10” (25.4 cm) hole or square on the wall.

Cut the hole from the interior through the exterior wall surfaces.

4. Frame the hole as shown in Figure 29.
5. Trim the wall thimble to match the wall thickness as necessary. Install the wall thimble and secure

Please read and understand these instructions before installing. Failure to follow

these instructions carefully could cause property damage or personal injury.

F

IREPLACE

H

ORIZONTAL

V

ENT

K

IT

50-1235: