Initial installation – Enviro DV36 User Manual

Page 23

Advertising
background image

23

Wall framing

Horizontal wall

termination

Wall thimble

fire stop

Exhaust

flex pipe

Combustion air

outer pipe

Elbow

Initial Installation

QUALIFIED INSTALLERS ONLY

H

ORIZONTAL

T

ERMINATION

:

NOTES:
1. Horizontal pipes must not be level. For every 12 inches (305 mm) of horizontal travel

(away from the stove), there should be at least 1⁄4 inch (6.4 mm) of vertical travel. Never

allow the vent to run downward, as this could cause high temperatures or even present

the possibility of a fire.

2. The exterior of the horizontal

vent termination must not be

blocked or obstructed.

3. If the vent termination is not

being attached to wood, the

four wood screws provided

should be replaced with

material appropriate fasteners.

4. For buildings with vinyl siding,

a vinyl standoff should be

installed between the vent cap

and the exterior wall. Attach

the vinyl siding standoff to

the horizontal termination.

Note that the termination

bolts onto the flat portion of

the standoff, providing an air

space between the wall and

the vent termination. The air

gap prevents excessive heat

from possibly melting the vinyl

siding.

5. Horizontal pipes must be

supported every 3 feet (914
mm). Plumber’s all round strap will suffice.

6. When running horizontal pipe, clearances to combustibles must be maintained 11⁄2 inches (38 mm)

sides, 11⁄2 inches (38 mm) bottom, and 2 inches (51 mm) top.

Step 1. Set the fireplace in the desired location. Check to determine if wall studs will be in the way when

the venting system is attached. If this is the case, the location of the fireplace may have to be

adjusted or the venting may have to be offset.

Step 2. Direct vent pipe sections are designed with special twist-lock connections. Dry fit the desired

combination of pipe and elbows to the appliance adaptor.

Step 3. With the pipe in the correct position and attached to the fireplace, mark the wall for a 10 inches

(25.4 cm) x 10 inches (25.4 cm) square hole (see Figure 29). The center of the hole should

match the center line of the horizontal pipe. Cut and frame the hole in the exterior wall where

the vent will be terminated. If the wall being penetrated is made of a non-combustible material

(i.e. masonry or concrete) a 7 inches (17.8 cm) hole is acceptable.

Figure 33. Horizontal Vent Termination

Advertising