V. Replacement of Components

WARNING

1. This unit should be diagnosed and repaired only by qualified service

personnel to reduce the risk of death, electric shock, serious injury, or fire.

2. Move the control switch to the "OFF" position and turn off the power supply

before servicing. Lockout/Tagout to prevent the power from being turned back
on inadvertently.

3.

CHOKING HAZARD: Ensure all components, fasteners, and thumbscrews
are securely in place after the unit is serviced. Make sure that none have
fallen into the storage bin.

4. Make sure all food zones in the icemaker and storage bin are clean after

the unit is serviced. For cleaning procedures, see "VI. Cleaning and
Maintenance."

A. Service for Refrigerant Lines

WARNING

1. Repairs requiring the refrigeration circuit to be opened must be performed by

properly trained and EPA-certified service personnel.

2. Always recover the refrigerant and store it in an approved container. Do not

discharge the refrigerant into the atmosphere.

3. Use an electronic leak detector or soap bubbles to check for leaks. Add a

trace of refrigerant to the system (if using an electronic leak detector), and
then raise the pressure using nitrogen gas (140 PSIG). DO NOT use R-404A
as a mixture with pressurized air for leak testing.

CAUTION

1. Do not leave the system open for longer than 15 minutes when replacing or

servicing parts. The Polyol Ester (POE) oils used in R-404A units can absorb
moisture quickly. Therefore it is important to prevent moisture from entering
the system when replacing or servicing parts.

2. Always install a new drier every time the sealed refrigeration system is

opened.

3. Do not replace the drier until after all other repair or replacement has been

made. Install the new drier with the arrow on the drier in the direction of the
refrigerant flow.

4. When brazing, protect the drier by using a wet cloth to prevent the drier from

overheating. Do not allow the drier to exceed 250°F (121°C).

1. Refrigerant Recovery
The icemaker is provided with refrigerant service valves. Using proper refrigerant practices,
recover the refrigerant from the service valves and store it in an approved container. Do not
discharge the refrigerant into the atmosphere.