Connecting alarms, Ai 1 to 4 (alarm in), Gnd (ground) – Honeywell HRHD 410 User Manual

Page 30: Ai 1 to 4 (alarm in) gnd (ground), Figure 2-11, Alarm input connector strips

Advertising
background image

Installation

Rev 3.01

12

Document 900.0315

10/05

Note

When the DVR successfully resets to factory defaults all the LEDs
on the front panel flash three times.

5.

Release the reset switch. All of the DVR settings are now at the original settings it
had when it left the factory.

Connecting Alarms

Figure 2-11

Alarm Input Connector Strips

To make connections on the Alarm Connector Strip:

1.

Press and hold the button.

2.

Insert the wire in the hole below the button.

3.

After releasing the button, tug gently on the wire to make certain it is connected.

4.

To disconnect a wire, press and hold the button above the wire and pull out the
wire.

AI 1 to 4 (Alarm In)

You can use external devices to signal the DVR to react to events. Mechanical or
electrical switches can be wired to the AI (Alarm In) and GND (Ground) connectors. The
threshold voltage is for NC (Normally Closed) is above 4.3V and should be stable at
least 0.5 seconds to be detected. For NO (Normally Open), the threshold voltage is
below 0.3V. See

Chapter 3, Configuration

for configuring alarm input.

GND (Ground)

Connect the ground side of the Alarm input to the GND connector.