Start point y, P.15), Compensation changeover point w – Honeywell MICRONIK 200 R7426A User Manual

Page 10: P.03), Occupied/unoccupied function soffs (p.16), Setting guidelines for reset time of p+i control

Advertising
background image

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK

EN1B-0203GE51 R0507C

10

Setting Guidelines for Reset Time of P+I Control

The reset time tr should be adjusted to 2...3 times of the
response time T

u

, which is the time interval between the

beginning of a sustained disturbance (e.g. rapid step change
of valve position) and the instant when the resulting change in
the output signal reaches a specified fraction of its final
steady-state value, either before overshoot or in the absence
of overshoot.
The response time T

u

in discharge air control is normally in

the range of 0.1 to 0.6 min, which allows adjustments of the
reset time tr in a range of 0.2 to 2 min.
In room control the response time T

u

is in the range of

0.5 to 5 min, which results in a setting of 1 to 15 min.

Start Point Y

start

(P.15)

This control parameter is available only on the single output
controller R7426A and on the R7426B controller if the three 3-
position floating outputs are configured for 6-stage ON/OFF
sequence control and on the R7426B,C controllers if YMode
= 1 is selected.
The start point determines the midrange shift of the output Y1
from the calculated control point.
The start point is calibrated in degrees K and is the offset
(plus or minus) from the set values or calculated control
points at which the output Y1 is at 50%. Normally and
especially in P+l control, the start point should be set at zero.
A change is required only in specific applications where a
asymmetrical arrangement results in improved control per-
formance, e.g. if for heat-up of a large space in the morning a
high heat capacity is needed and for normal control the valve
must be opened by only a small amount.

Compensation Changeover Point W

comp

(P.03)

The control parameter W

comp

defines the start point of

summer or winter compensation. Above the compensation
changeover point (W

comp

) summer compensation and below

W

comp

winter compensation is performed.

Summer / Winter Compensation Authority

Su / Wi (P.04 / P.05)

These authority settings determine the reset effect (OAT

Comp

)

the compensation sensor (T3) has on the main setpoint W1 in
percentages. Outside temperature reset in summer and
winter time are commonly used applications.
To calculate winter and summer authority, the throttling range
must be considered in proportional-only control according to
Table 12.

Table 12. Calculation of summer/winter compensation

control

schedule

room temp.

(T1)

outdoor air

temp.

(T3/T

comp

)

throttling

range (X

P

)

20

°C 20°C 2°C

22

°C -15°C 2°C

Winter

Aut Wi =

T1 X

t Outside Air

100%

p

+

=

(22 - 20) + 2

35

100%

12%

=≈

20

°C 20°C 2°C

26

°C 35°C 2°C

Summer

Aut Su =

T1 X

t Outside Air

100%

p

=

(26 - 20) - 2

15

100%

27%

=≈

Compensation change-over at +20

°C outdoor air temperature

NOTE: With P+I control X

p

= 0

Occupied/Unoccupied Function SOFFS

(P.16)

A potential-free contact can be used between terminals 1 and
4 to switch the controller between occupied (contact closed)
or unoccupied (contact open) mode.
In occupied mode, the temperature set point W1 is used for
the control point calculation. In unoccupied mode, the SOFFS
parameter value is added (cooling) to or subtracted (heating)
from the calculated control point.
In the case of the R7426A controller, the parameter Y1CTRF
must be set to 0 or 1 (

≠ Cho) to match the required heating or

cooling application.
If the configuration parameter Y1CTRF is set to 2 (summer /
winter changeover), the parameter SOFFS is not considered.
In sequence applications of heating and cooling, the SOFFS
parameter value is added to the control point for cooling
(CTRPC) and subtracted from the control point for heating
(CTRPH) (see Fig. 5).

Night Mode Offset NOFFS

(P.26: Controller with RTC only)

This control parameter is used to set the night mode offset.
During night mode, freeze protection is active and the
occupied / unoccupied function is inactive.

Night Cycle NightLow and NightHigh

(P.24 and P.25: with RTC, only)

The control parameters NightLow and NightHigh are used
by the night cycle program (controller mode = OFF) to assign
unoccupied night low or high limits for the protection of a
space and its contents against temperature extremes.

Advertising
This manual is related to the following products: