Selecting Clock and Schedules (with RTC, only)

DATE & TIME

SELECTION

STANDARD

SCHEDULE

SELECTION

HOLIDAY

SCHEDULE

SELECTION

STANDARD

SCHEDULE

PROGRAMMING

DATE & TIME

ADJUSTMENT

HOLIDAY

SCHEDULE

PROGRAMMING

Fig. 13. Clock and schedules selection mode


The clock and schedule selection mode is provided to select
real-time clock (RTC), standard schedule (SCH), or holiday
schedule (Hol) for programming (see Fig. 13).

Pushing the

+

or

-

button scrolls through the selection list.

Adjusting Date and Time (with RTC, only)

This mode is used to adjust date and time (real-time clock) by
the input sequence shown in Fig. 14.
During date adjustment, the weekday is calculated auto-
matically and need not be programmed. The 29th of February
is adjustable only for leap years.
Pushing the SEL button returns to the selection mode,
ignoring adjustments which have not been confirmed by the
SET

button.

Due to battery change or low battery, the date / time can be
invalid and is displayed as --.--. -- / --:-- on the LCD. In this
case the controller behaves like a controller without real-time
clock. If the occupancy input is inactive, the controller will be
assumed as occupied.

Date

Date

Date

TO ADJUST

YEAR

OR

TO ADJUST

MONTH

OR

TO ADJUST

DAY

OR

TO ADJUST

MINUTES

OR

TO ADJUST

HOURS

OR

TIM

E A

D

JU

ST

ME

NT

DA

TE

A

D

JU

ST

M

ENT

Fig. 14. Date and time adjustment mode

Programming Standard Schedule (with RTC, only)

The standard schedule programming is used to program up to
6 schedule points for each weekday as well as for three
holiday types. The controller mode (off, night, standby or
comfort) will be switched at these programmed schedule
points.
The first step of the schedule programming (see Fig. 15) is to
select a weekday or holiday type as follows:
1. Mo ... Su as single
2. H1 ... H3 as single
3. Mo ... Fr grouped
4. Sa and Su grouped
5. Mo ... Su grouped
The switching time is adjustable in steps of 10 min. To ignore
a schedule point, the displayed switching time must be set to
--:--’ by adjusting it between step 23:50 and 0:00 or by
pushing the

+

and

-

button simultaneously.

Pushing the SEL button returns to the selection mode,
ignoring adjustments which have not been confirmed by the
SET

button.

TO ADJUST

SWITCHING

TIME

OR

TO ADJUST

CONTROLLER

MODE

OR

TO ADJUST

SCHEDULE

POINT

OR

TO SELECT

WEEKDAY,

WEEK GROUPS,

OR HOLIDAY

TYPES

OR

Tu

Tu

Tu

Fig. 15. Standard schedule programming