R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

EN1B-0203GE51 R0507C

4

config. par.

R7426

no.

name

description

default
setting

I / II

A B C

actual

value

C.12 T2ext

Enable / Disables the T1 sensor input to be used for both T1 and T2 inputs.

0 x

x

x

0

1

T2 installed

T1 signal used for T2

C.13 LimTyp

Limitation type determines whether the limit function is low or high.

0 / 1

x x x

0

1

Low limit

High limit

C.14 Senstyp

Sensor type determines automatic detection or manual selection of NTC

sensors.

0 x

x

x

0

1

Auto detection

NTC sensor type

C.15 Y1CTRF

Controls the action of Y1 or activates the occupancy input for summer/winter

changeover.

0 / 1

x x x

R7426A R7426B,C

0

1

2

cooling

heating

summer/winter changeover

0

1

mixed air damper

energy recovery

C.16 AddHour

2)

Adjusts the month for winter/summer time change.

3 x

x

x

Min.

Max.

0 (disables winter/summer time change)

12

(

March

)

C.17 SubHour

2)

Adjusts the month for summer/winter time change.

10 x

x

x

Min.

Max.

0 (disables summer/winter time change)

12

(

Oct

.)

C.18

PSTG_H

2) 3)

Determines the prestart gradient to reach the comfort setpoint for heating.

0 K/min x x x

Min.

Max.

0 (disabled)

2

C.19

PSTG_C

2) 3)

Determines the prestart gradient to reach the comfort setpoint for cooling.

0 K/min x x x

Min.

Max.

0 (disabled)

2

C.20 tvd

2)

Determines the damper prestart time before scheduled comfort mode

15 min

x x

Min.

Max.

0 (normal control)

90

C.21 Adapt

2)

Optimum Start Self Adaption speed

50% x

x

x

Min.

Max.

0

100

C.22 Adr

1)

Sets the serial communication address, used for service or maintenance.

254 x

x

x

Min.

Max.

0

255

C.23 DefProg

Initiates the default programming.

0 x

x

x

0

1

No Default programming

Initiates Default programming

1)

actual value will not be changed during reset to default parameter

2)

on Controllers with Real-Time Clock, only

3)

can be overwritten by controller for self-adaption purposes, resolution = 0.01 K/min

For detailed information of configuration parameters see chapter Configuration Settings.