R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

EN1B-0203GE51 R0507C

14

Displaying Actual Values

In the standard display mode, one of nine actual values, the
actual time, or the date can be selected and displayed by
pushing the SEL button.
The icons of the permanently displayed controller mode are
described in the following table:

Table 13. Icons

controller mode / status

display

Off

OFF - icon

Night

1)

Moon - icon

Standby

Halfsun - icon

Comfort

Sun - icon

Freeze Protection Alarm and
Operation

2)

Freeze protection icon in
addition

Low battery

1) 2) 3)

Battery

icon

Optimum Start

1)

Sun icon is flashing

≈ 1Hz

1)

On controllers with real-time clock, only.

2)

Status information is displayed together with actual icon

for the controller mode.

3)

In order to improve battery lifetime, low battery detection

is performed only once a day and after power up.

If a displayed date is programmed to be a holiday, the
corresponding holiday icon is displayed on controllers with
real-time clock.

Selecting Parameters

The parameter/configuration selection mode is used to select
control and configuration parameters (Fig. 9) for adjustment.
The displayed parameter no. corresponds with the number in
Table 4 and Table 5. Default programming is indicated by a
display of def.

Pushing the

+

or

-

button scrolls through the parameter list.

Pushing the SET button enters the adjustment mode.

Adjusting Configuration / Parameter Values

The adjustment mode is used to adjust configuration and
parameter values (Fig. 10). In this mode, the selected para-
meter no. is displayed and the corresponding value flashes.

Pushing the

+

or

-

button increments or decrements the value

of the selected parameter. Ranges are shown in Table 4 and
Table 5. An adjustment example is shown in Fig. 18.
Pushing the SEL button retains the old parameter value.
Pushing the SET button accepts the parameter value and
returns to parameter/configuration selection mode.

Resetting Param. Values to Default Values

Pushing simultaneously the

+

and

-

button during the power

up or setting the control parameter DefProg to 1 resets all
control and configuration parameters to defaults (see Table 4
and Table 5). Default programming is indicated by a display of
def.

°C

°C

FIRST DISPLAYED CONFIGURATION

PARAMETER:

ACTUAL

PARAMETER

VALUE

FOR R7426C

FOR R7426A,B

NOTE: CONTROL OR CONFIGURATION

PARAMETERS WHICH ARE NOT

AVAILABLE ON THE GIVEN
CONTROLLER VERSION ARE

SKIPPED.

Fig. 9. Parameter/Configuration Selection Mode

TO ADJUST

PARAMETER

VALUE

°C

OR

Fig. 10. Parameter/Configuration Adjustment Mode

Selecting Output Values

The output selection mode is used to select the output no.
(see Fig. 11) for manual override adjustment. An activated
manual override is indicated by a displayed F (fixed).

Pushing the

+

or

-

button scrolls through the output list.

Pushing the SET button enters the adjustment mode.

Manually Overriding Output Values

The output adjustment mode is used for manual override
adjustment of output values (see Fig. 12). In this mode, the
selected output no. is displayed and the actual output value
flashes.

Pushing the

+

or

-

button increments or decrements the value

of the selected output for manual override purpose. The
output range is displayed in correspondence with the nominal
control range.
To return to output selection mode, three options are
available:
• Pushing

the

SET

-button after adjustment activates the

manual override (fixing) of output value.

• Pushing

the

SEL

button, causes that the output value is

still determined by the control loop (no fixing).