R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

EN1B-0203GE51 R0507C

18

Programming Holiday Schedule (with RTC, only)

The holiday schedule programming is used to program each
day of the year (01.01 ... 31.12.) as a holiday (day type = H1,
H2 or H3) or as a normal day (day type = H0 is default).

Pushing the

+

or

-

button during the first step of the holiday

programming (see Fig. 16) toggles between all programmed
holidays (

≠ H0) and displays them (type and date).

If none of the 365 days of a year is programmed to be a
holiday, the actual date is displayed, marked as normal day
(H0).
Pushing the SET button selects the displayed holiday and
enters the adjustment for date and day type.
To program a new holiday, select any holiday, adjust date
(and holiday type if necessary) and confirm the changes by
pushing the SET button. To reset a holiday to normal day, day
type H0 has to be set for the specific day.
Pushing the SEL button returns to the selection mode,
ignoring adjustments which have not been confirmed by the
SET

button.

TO ADJUST

DAY

OR

TO ADJUST

DAY TYPE (H0,

H1, H2, OR H3)

OR

TO ADJUST

MONTH

OR

TO

TOGGLE/DISPLAY

PROGRAMMED

HOLIDAY

OR

We

We

Th

Sa

Fig. 16. Holiday schedule programming

Interpreting Error Messages

Different analog input errors can be identified by the controller
(Error handling). The defective analog input (T1, T2, T3 or
X

wrh

) will be displayed in the standard display mode (see Fig.

17) after the corresponding value is selected.
NOTE:

For the external CPA/SPA potentiometer input, no

error message is indicated if the potentiometer or
wiring is defective. In this case, for control point or
setpoint calculation, the following values are used:

• for CPATYP 0, 1 or 2 ⇒ CPA value = 0
• for CPATYP 3 ⇒ SPA value = control parameter W1

STANDARD

DISPLAY

DISPLAY SHOWN IF NO SENSOR

IS CONNECTED DURING POWER-UP

TEMPERATURE DISPLAY IN

°C

HUMIDITY DEVIATION DISPLAY IN % rh

DISPLAY SHOWN AFTER ERROR

IDENTIFICATION DURING OPERATION

STANDARD

DISPLAY

AND

: MAIN TEMPERATURE SENSOR T1 IS DEFECTIVE

: LIMITATION OR CASCADE TEMPERATURE SENSOR T2 IS DEFECTIVE

: COMPENSATION TEMPERATURE SENSOR T3 IS DEFECTIVE

: ERROR OF HUMIDITY DEVIATION INPUT X

Wrh

AND

AND

AND

SPACE

°C

% rh

°C

% rh

Fig. 17. Error handling

PARAMETER

SELECTION

MODE

PARAMETER

SELECTION

MODE

PARAMETER

ADJUSTMENT

MODE

STANDARD

DISPLAY

MODE

PUSH

SIMULTANEOUSLY

FOR APPROX.

2 SEC

PUSH UNTIL

NEEDED

VALUE IS

DISPLAYED

A

B

A

B

THIS EXAMPLE DESCRIBES THE ADJUSTMENT OF THE

COMPENSATION CHANGEOVER POINT W

(P03).

comp

°C

°C

°C

°C

°C

Fig. 18. Adjustment example