R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL TIME CLOCK

EN1B-0203GE51 R0507C

12

Changing Operating Modes

Fig. 7 shows the six operating modes. After power-up the
controller version is displayed and the controller enters the
standard display mode. In this mode, selected input or output
values and on controllers with real-time clock the time or the
date are displayed. The controller mode is permanently
displayed by a corresponding icon (Fig. 6).

Pushing the

+

and

-

button simultaneously for approximately

1 sec causes the controller to leave the standard display
mode and to enter the parameter/configuration selection
mode (Fig. 9). This mode is used for application configuration
and to select parameters for adjustment.
Pushing the SET button causes the controller to accept the
selected parameter or configuration no. and to enter the ad-
justment mode (Fig. 10), which is used to adjust configuration
/ parameter values. After adjustment, the controller returns to
selection mode by pushing the SET or SEL button. Pushing
the SEL button leads back to standard display mode.

Pushing the SET and SEL button simultaneously for approx.
1 sec causes the controller to leave the standard display
mode and to enter the output data selection mode (Fig. 11).
Pushing the SET button causes the controller to accept the
selected output data no. and to enter the output adjustment
mode (Fig. 12). This mode is used for manual override of
output values. The return to standard display mode is shown
in Fig. 7.

Pushing the SET and

-

button simultaneously for approx.

1 sec causes the controller to leave the standard display
mode and to enter the clock / schedule selection mode (Fig.
13) on controllers with real-time clock, only.




OUTPUT

ADJUSTMENT

MODE

STANDARD

DISPLAY

MODE

CLOCK /

SCHEDULE

SELECTION

PARAM./CONFIG.

SELECTION

MODE

PARAM./CONFIG.

ADJUSTMENT

MODE

OUTPUT

SELECTION

MODE

OUTPUT

FIXING

NO OUTPUT FIXING

AND

AUTOMATIC

DISPLAY

POWER UP

FOR APPROX.

1 SEC

FOR APPROX.

1 SEC

FOR APPROX.

1 SEC

NO PARAMETER

VALUE CHANGE

RELEASE OF

OUTPUT FIXING

AND

AND

CONTROLLERS WITH

REAL-TIME

CLOCKS, ONLY.

Fig. 7. Operating overview