Honeywell MICRONIK 200 R7426A User Manual

Page 5

Advertising
background image

R7426A,B,C TEMPERATURE CONTROLLER WITH AND WITHOUT REAL-TIME CLOCK

5

EN1B-0203GE51

R0507C

control par.

setting I / setting II

R7426

no. name

description

low

high def.

reso-

lution

unit

A B C

actual

value

P.01 W1

Main setpoint for input T1

0

50 /

130

21 /

70

0.5

°C x x x

P.02 Wlim

Limit setpoint (low or high) for input T2

5 /

30

50 /

130

16 /

90

1

°C x x x

P.03 Wcomp

Compensation changeover point for input T3

-5

40

20

1

°C x x x

P.04 Wi

Winter compensation authority -350

+350

0

2

%

x

x x

P.05 Su

Summer compensation authority -100

+100

0

1

%

x

x x

P.06 Wcas

Submaster or cascade setpoint

OFF, 0

50

20

0.5

°C x x x

P.07 Rcas

Cascade reset span adjustment

0

40

10

0.5

K

x x x

P.08 Xp1

Throttling range (main control loop) for T1

0.5

40

2

0.5

K

x x x

P.09 Xp2

Throttling range (cascade or limit control loop)

for T2

0.5 40

10

0.5 K

x

x x

P.10 Xpc

Cooling throttling range for sequence control

OFF, 1

40

3

0.5

K

x x

P.11 Xph

Heating throttling range for sequence control

1

40

6

0.5

K

x x

P.12 tr1

1)

Reset time (main control loop)

OFF,

20 sec

20

min

OFF

10/

0.5

sec/

min

x x x

P.13 tr2

1)

Reset time (cascade control loop)

OFF,

20 sec

20

min

OFF

10/

0.5

sec/

min

x x x

P.14 MINPOS

Minimal pos. for air damper actuators

0

50

20

1

%

x x

P.15 Ystart

Start point for mid range shift of output Y1

-20

+20

0

0.5

K

x x x

P.16 SOFFS

Offset of main setpoint in Standby mode

0

10

2

0.1

K

x x x

P.17 T1Cal

Calibration of temperature sensor T1

-20

+20

0

0.1

K

x x x

P.18 T2Cal

Calibration of temperature sensor T2

-20

+20

0

0.1

K

x x x

P.19 T3Cal

Calibration of temperature sensor T3

-20

+20

0

0.1

K

x x x

P.20 RetOffs

Return air offset to simulate exhaust air cond.

OFF, 0

5

OFF

0.1

K

x x

P.21 RuntimeY1 Actuator run time for Y1

6

180

60

1

sec x x

P.22 RuntimeY3 Actuator run time for Y3

6

180

60

1

sec

x

P.23 RuntimeY2 Actuator run time for Y2

6

180

60

1

sec

x

P.24 NightLow

2)

Night low limit against temperature extremes

OFF, 8

19

OFF

1

°C x x x

P.25 NightHigh

2)

Night high limit against temperature extremes OFF, 21

40

OFF

1

°C x x x

P.26 NOFFS

2)

Offset of main setpoint in Night mode

0

30

5

0.1

K

x x x

1)

for tr > 2 min

⇒ resolution = 0.5 min, for tr < 2 min ⇒ resolution = 10 sec

2)

on Controllers with Real-Time Clock, only

For detailed information of control parameters see chapter Parameter Settings and Adjustment.

Table 5. Control parameters R7426A,B,C