Vent information and diagrams, A. approved pipe, C. use of elbows – Heat & Glo Fireplace 8000CF-OAK-IPI User Manual

Page 23: B. vent table key, D. measuring standards

Advertising
background image

Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev. R • 6/09

23

A. Approved Pipe

This appliance is approved for use with Hearth & Home

Technologies DVP venting systems. Refer to Section 16B

for vent component information.
DO NOT mix pipe, fi ttings or joining methods from differ-

ent manufacturers.
The pipe is tested to be run inside an enclosed wall.

There is no requirement for inspection openings at each

joint within the wall.
WARNING! Risk of Fire or Asphyxiation. This appli-

ance requires a separate vent.

DO NOT vent to a pipe

serving a separate solid fuel burning appliance.

C. Use of Elbows

Diagonal runs have both vertical and horizontal vent as-

pects when calculating the effects. Use the rise for the

vertical aspect and the run for the horizontal aspect (see

Figure 7.1).
Two 45º elbows may be used in place of one 90º elbow.

On 45º runs, one foot of diagonal is equal to 8-1/2 in. (216

mm) horizontal run and 8-1/2 in. (216 mm) vertical run. A

length of straight pipe is allowed between two 45º elbows

(see Figure 7.1).

Figure 7.1

7

Vent Information and Diagrams

B. Vent Table Key

The abbreviations listed in this vent table key are used in

the vent diagrams.

D. Measuring Standards

Vertical and horizontal measurements listed in the vent

diagrams were made using the following standards.
• Pipe measurements are shown using the effective length

of pipe (see Figure 7.2).

• Horizontal terminations are measured to the outside

mounting surface (fl ange of termination cap) (see Figure

6.3).

• Vertical terminations are measured to bottom of

termination cap.

• Horizontal pipe installed level with no rise.

Figure 7.2 DVP Pipe Effective Length

Effective

Height/Length

Symbol

Description

V

1

First section (closest to appliance) of vertical length

V

2

Second section of vertical length

H

1

First section (closest to appliance) of horizontal length

H

2

Subsequent sections of horizontal length

Horizontal

Vertical

8-1/2 in.

8-

1/

2 i

n.

12 i

n.

Pipe

Effective Length

Inches

Millimeters

DVP4

4

102

DVP6

6

152

DVP12

12

305

DVP24

24

610

DVP36

36

914

DVP48

48

1219

DVP6A

3 to 6

76 to 152

DVP12A 3 to 12 76 to 305

DVP12MI 3 to 12 76 to 305
DVP24MI 3 to 24 76 to 610