D. Install Attic Insulation Shield

WARNING! Fire Risk. DO NOT allow loose materials or

insulation to touch vent. Hearth & Home Technologies

Inc. requires the use of an attic shield.
The National Fuel Gas Code ANSI Z223.1 and NFPA 54

requires an attic shield constructed of 26 gauge minimum

metal that extends at least 2 in. (51 mm) above insulation.
Attic shields must meet specifi ed clearance and be se-

cured in place.
Flat Ceiling Installation
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make

room for the attic insulation shield.
• Wrap shield around pipe if pipe is already installed in

area to be insulated.

• Match the three holes in each side and fasten with three

screws to form a tube.

• Bend three tabs on the bottom of the shield outward to

allow attachment to the ceiling fi restop.

• Bend the remaining bottom tabs inward 90º to maintain

the air space between the pipe and the shield. Set the

shield on the ceiling fi restop and attach to the fi restop.

• Bend all tabs inward 90º around the top of the shield.

These tabs must be used to prevent blown insulation

from getting between the shield and vent pipe, and to

maintain air space clearance.

Figure 8.9 Attic Insulation Shield

Vaulted Ceiling Installation
• Remove one shield from box.
NOTICE: Cut previously installed batt insulation to make

room for the attic insulation shield.
• Cut the attic insulation shield (if application is for vaulted

ceiling) to fi t your ceiling pitch. Snip cut edge to recreate

1 in. bend tabs all the way around the bottom.

• Wrap shield around pipe if pipe is already installed in

area to be insulated.

• Match the three holes in each side and fasten with three

screws to form a tube.

• Bend three tabs on the bottom of the shield outward to

allow attachment to the ceiling fi restop.

• Bend the remaining bottom tabs inward 90º to maintain

the air space between the pipe and the shield. Set the

shield on the ceiling fi restop and attach to the fi restop.

• Bend all tabs inward 90º around the top of the shield.

These tabs must be used to prevent blown insulation

from getting between the shield and vent pipe, and to

maintain air space clearance.

BEND ALL TABS INWARD 90°

TO MAINTAIN CLEARANCE

AND PREVENT INSULATION

FROM FALLING INSIDE

INSERT 3

SCREWS

BEND 3 TABS

OUTWARD TO

FASTEN TO CEILING

FIRESTOP-BEND

REMAINING TABS

INWARD 90 DEGREES

TO MAINTAIN

CLEARANCE