Vent clearances and framing, Warning, A. pipe clearances to combustibles – Heat & Glo Fireplace 8000CF-OAK-IPI User Manual

Page 28

Advertising
background image

Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev. R • 6/09

28

A. Pipe Clearances to Combustibles

WARNING! Risk of Fire! Maintain air space clearance to

vent.

DO NOT pack insulation or other combustibles:

• Between ceiling fi restops

• Between wall shield fi restops

• Around vent system
Failure to keep insulation or other material away from

vent pipe may cause over heating and fi re.

8

Vent Clearances and Framing

COMBUSTIBLE SURFACE

CORRECT

INCORRECT

DIRECTION

UP

HEAT SHIELD

90º ELBOW

Fire Risk.
Installation of this appliance may require the

use of heat shield 385-290 above the fi rst 90º

elbow in the venting system.

Heat Shield Above First 90

0

Elbow

Figure 8.2

Figure 8.3

Fasten the shield in place using the four pilot holes pro-

vided in the part.
• Position the shield so the longest dimension (13 1/2

inch) is placed in same direction the elbow is pointing.

• Center the shield directly above the elbow with a 1/2

inch air space between shield and combustible surface

(see Figure 8.3).

• Heat shield required if vertical distance between top of

horizontal elbow and any combustible surface above

elbow is less than 4 inches.

• Heat shield not required if distance is more than 4

inches.

HEAT

SHIELD

3 IN. MIN.

(76 mm)

COMBUSTIBLE

SURFACE

Figure 8.1 Pipe Clearances

1 in. CLEARANCE

AROUND VERTICAL

SECTIONS

3 in. TOP

CLEARANCE

1 in. SIDE AND

BOTTOM CLEARANCE

Note: Slope not

required.

WARNING

• Attach elbow heat shield to the exhaust pipe if combusti-

ble materials are not present at install (see Figure 8.4).

• Cut the tabs as shown and bend down. Using the screws

found in the manual bag secure the heat shield to the pipe

maintaining 3 to 4 inches between the pipe and shield.

SCREW

3 in.

(76 mm)

Figure 8.4