Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev. R • 6/09

8

H. Requirements for the Commonwealth of

Massachusetts

For all side wall horizontally vented gas fueled equipment

installed in every dwelling, building or structure used in

whole or in part for residential purposes, including those

owned or operated by the Commonwealth and where the

side wall exhaust vent termination is less than seven (7)

feet above fi nished grade in the area of the venting, in-

cluding but not limited to decks and porches, the following

requirements shall be satisfi ed:

Installation of Carbon Monoxide Detectors
At the time of installation of the side wall horizontal vented

gas fueled equipment, the installing plumber or gas fi tter

shall observe that a hard wired carbon monoxide detector

with an alarm and battery back-up is installed on the fl oor

level where the gas equipment is to be installed. In addi-

tion, the installing plumber or gas fi tter shall observe that

a battery operated or hard wired carbon monoxide detec-

tor with an alarm is installed on each additional level of

the dwelling, building or structure served by the side wall

horizontal vented gas fueled equipment. It shall be the

responsibility of the property owner to secure the services

of qualifi ed licensed professionals for the installation of

hard wired carbon monoxide detectors.

In the event that the side wall horizontally vented gas fu-

eled equipment is installed in a crawl space or an attic,

the hard wired carbon monoxide detector with alarm and

battery back-up may be installed on the next adjacent

fl oor level.

In the event that the requirements of this subdivision can

not be met at the time of completion of installation, the

owner shall have a period of thirty (30) days to comply

with the above requirements; provided, however, that dur-

ing said thirty (30) day period, a battery operated carbon

monoxide detector with an alarm shall be installed.

Approved Carbon Monoxide Detectors
Each carbon monoxide detector as required in accor-

dance with the above provisions shall comply with NFPA

720 and be ANSI/UL 2034 listed and IAS certifi ed.

Signage
A metal or plastic identifi cation plate shall be permanent-

ly mounted to the exterior of the building at a minimum

height of eight (8) feet above grade directly in line with the

exhaust vent terminal for the horizontally vented gas fu-

eled heating appliance or equipment. The sign shall read,

in print size no less than one-half (1/2) in. in size,

“GAS

VENT DIRECTLY BELOW. KEEP CLEAR OF ALL OB-

STRUCTIONS”.

Inspection
The state or local gas inspector of the side wall horizon-

tally vented gas fueled equipment shall not approve the

installation unless, upon inspection, the inspector ob-

serves carbon monoxide detectors and signage installed

in accordance with the provisions of 248 CMR 5.08(2)(a)1

through 4.

Exemptions
The following equipment is exempt from 248 CMR

5.08(2)(a)1 through 4:
• The equipment listed in Chapter 10 entitled “Equipment

Not Required To Be Vented” in the most current edition

of NFPA 54 as adopted by the Board; and

• Product Approved side wall horizontally vented gas fu-

eled equipment installed in a room or structure separate

from the dwelling, building or structure used in whole or

in part for residential purposes.

MANUFACTURER REQUIREMENTS

Gas Equipment Venting System Provided
When the manufacturer of Product Approved side wall

horizontally vented gas equipment provides a venting

system design or venting system components with the

equipment, the instructions provided by the manufacturer

for installation of the equipment and the venting system

shall include:
• Detailed instructions for the installation of the venting

system design or the venting system components; and

• A complete parts list for the venting system design or

venting system.

Gas Equipment Venting System NOT Provided
When the manufacturer of a Product Approved side wall

horizontally vented gas fueled equipment does not pro-

vide the parts for venting the fl ue gases, but identifi es

“special venting systems”, the following requirements

shall be satisfi ed by the manufacturer:

• The referenced “special venting system” instructions

shall be included with the appliance or equipment in-

stallation instructions; and

• The “special venting systems” shall be Product Ap-

proved by the Board, and the instructions for that sys-

tem shall include a parts list and detailed installation

instructions.

A copy of all installation instructions for all Product Ap-

proved side wall horizontally vented gas fueled equip-

ment, all venting instructions, all parts lists for venting

instructions, and/or all venting design instructions shall

remain with the appliance or equipment at the completion

of the installation.

See Gas Connection section for additional Common-

wealth of Massachusetts requirements.

Note: The following requirements reference various

Massachusetts and national codes not contained in this

document.