C. install the ceiling firestop – Heat & Glo Fireplace 8000CF-OAK-IPI User Manual

Page 30

Advertising
background image

Heat & Glo • 8000CF-OAK-IPI • 2059-900 Rev. R • 6/09

30

C. Install the Ceiling Firestop

A ceiling fi restop

MUST be used between

fl oors and attics.

DVP pipe only - Frame an opening 10 in.

by 10 in. (254 mm by 254 mm) whenever

the vent penetrates a ceiling/fl oor (see

Figure 8.7).

• Frame the area with the same sized lumber

as used in ceiling/fl oor joist.

• The ceiling fi restop may be installed above or

below the ceiling joists when installed with a

attic insulation shield. It must be under joists

between fl oors that are not insulated. Refer

to Figure 8.8.

• Secure with three fasteners on each side.
WARNING! Risk of Fire! DO NOT pack insu-

lation around the vent. Insulation must be kept

back from the pipe to prevent overheating.

Figure 8.7 Installing Ceiling Firestop

Figure 8.8 Installing the Attic Shield

3 FASTENERS

PER SIDE

INSTALL ATTIC INSULATION SHIELDS

BEFORE OR AFTER INSTALLATION OF VENT SYSTEM

CEILING FIRESTOP

INSTALLED BELOW CEILING

CEILING FIRESTOP

INSTALLED ABOVE CEILING

ATTIC ABOVE

A

PIPE
DVP

A

10 in. (254 mm)

A

Advertising
This manual is related to the following products: