Technical specifications, 7 technical specifications – Honeywell ISM BAND XYR 5000 LINE User Manual

Page 41

Advertising
background image

7 Technical

Specifications

Power Characteristics

• 10VDC-30VDC, 24 VDC @ 200mA typical

RF Characteristics

• 902 MHz – 928 MHz Frequency Hopping Spread Spectrum (FHSS), FCC certified

ISM license-free band

Up to 3000’ range to Transmitters with clear line of sight; 500’ to 1000’ range with obstructions

• The RF module in each Transmitter is individually tested and calibrated over the full

temperature range to ensure reliable wireless operation

Output Options

• RS-485 digital communications with conversion to RS-232 or USB for interface with

PC or server and WMT (WMT) (optional)

Serial

Modbus RTU (Binary) over RS-485

Modbus

over TCP/IP (via optional converter)

Physical Characteristic

Baked

enamel explosion-proof, weather-proof and corrosion-proof housing

Electromagnetic

Compatibility

(CE

Compliance

)

• Operates within specification in fields from 80 to 1,000 MHz with field strengths to 10

V/m. Meets EN 50082-1 general immunity standard and EN 55011 compatibility
emissions standard

Industrial Certification

Rated for industrial use FM rated: -40°F to 185°F(-40°C to 85°C)

CSA Rated: -40°F to

104°F(-40°C to 40°C)

FM Approved as explosion-proof (XP) for Class I, Division 1, Groups B,C,&D, T6; as
dust ignition-proof for Class II/III, Division 1, Groups E, F, &G, T6; indoor and outdoor
(Type 4X)

hazardous (classified) locations.

CSA Approved as explosion-proof (XP) for Class I, Division 1, Groups B,C,&D, T6; as
dust ignition-proof for Class II/III, Division 1, Groups E, F, &G, T6; indoor and outdoor
(Type 4X)

hazardous (classified) locations.

NEMA

4X explosion-proof housing

34

Advertising