Table 7. Refrigerant Charge for Fan Cycling plus Flooded Condenser (lbs. R-22)

Model*

Summer

Charge

25° TD

20° TD

15° TD

10° TD

40°F

20°F

0°F

-20°F

40°F

20°F

0°F

-20°F

40°F

20°F

0°F

-20°F

40°F

20°F

0°F

-20°F

1

8

7

8

9

9

8

9

10

10

9

10

11

11

13

12

12

12

2

10

9

12

13

14

11

13

14

15

13

14

15

16

17

18

17

18

3

10

1

6

8

10

4

8

10

11

7

10

12

13

10

13

14

14

4

15

2

9

12

15

7

12

15

17

12

16

18

19

17

19

21

22

5

29

4

17

24

29

14

24

30

34

24

31

36

39

33

38

41

43

6

22

0

3

10

15

0

10

16

20

0

17

22

25

0

24

27

29

7

30

0

4

13

20

0

12

20

26

0

21

27

32

0

29

34

38

8

51

0

0

8

22

0

6

23

35

0

22

38

48

0

37

52

61

9

70

0

0

11

29

0

8

31

46

0

29

51

63

0

49

71

80

10

64

0

0

0

15

0

0

17

33

0

0

39

52

0

0

60

70

11

86

0

0

0

19

0

0

22

44

0

0

50

69

0

0

78

93

12

102

0

0

0

6

0

0

8

37

0

0

37

69

0

0

66

100

13

118

0

0

0

0

0

0

0

29

0

0

0

69

0

0

0

108

14

19

3

12

17

20

9

17

21

23

15

22

25

26

21

27

29

29

15

29

4

17

24

29

13

24

30

34

22

31

36

39

31

38

41

43

16

40

5

22

32

38

17

31

39

44

29

40

46

50

41

49

53

56

17

44

0

5

20

31

0

18

31

40

0

31

42

49

0

44

53

59

18

58

0

7

27

42

0

25

42

54

0

43

57

66

0

61

71

79

19

104

0

0

17

44

0

12

47

69

0

43

77

95

0

74

107

119

20

140

0

0

22

57

0

16

62

91

0

57

102

125

0

99

141

157

21

125

0

0

0

30

0

0

34

67

0

0

77

105

0

0

120

141

22

172

0

0

0

39

0

0

44

88

0

0

100

137

0

0

156

186

23

201

0

0

0

11

0

0

16

74

0

0

74

137

0

0

132

200

24

236

0

0

0

0

0

0

0

57

0

0

0

135

0

0

0

213

*.See.Model.Cross.Reference.Table.#10 .

Table 8. Refrigerant Charge. Lbs. R-22 for Flooded Condenser

Model*

Refrigerant R-22

Charge

for summer

Operation, Lbs.

Additional Refrigerant R-22 Charge Required for Flooded Condenser Operation Lbs. For

20°F TD Minimum Ambient at Condenser

+60

+40

+20

+0

-20

1

8

7

10

11

11

11

2

10

10

13

15

15

16

3

10

10

13

14

15

15

4

15

15

19

21

22

23

5

29

30

39

43

45

47

6

22

22

29

32

34

35

7

30

29

38

42

44

46

8

51

50

66

74

77

80

9

70

66

87

96

100

105

10

64

62

83

92

95

99

11

86

83

110

122

127

132

12

102

100

132

147

153

159

13

118

117

155

172

179

186

14

19

20

27

29

31

32

15

29

30

39

44

46

47

16

40

39

51

57

59

62

17

44

44

58

64

67

70

18

58

59

78

86

90

94

19

104

99

131

146

152

158

20

140

131

174

193

201

209

21

125

126

168

186

194

201

22

172

165

219

243

253

263

23

201

201

267

296

308

320

24

236

233

310

343

357

372

*.See.Model.Cross.Reference.Table.#10 .