Space and Location Requirements

The.most.important.consideration.which.must.be.taken.

into.account.when.deciding.upon.the.location.of.air-cooled.

equipment.is.the.provision.for.a.supply.of.ambient.air.to.the.

condenser,.and.removal.of.heated.air.from.the.condenser.area ..

Where.this.essential.requirement.is.not.adhered.to,.it.will.result.in.

higher.head.pressures,.which.cause.poor.operation.and.possible.

eventual.failure.of.equipment ..Units.must.not.be.located.in.the.

vicinity.of.steam,.hot.air.or.fume.exhausts .

Another.consideration.which.must.be.taken.is.that.the.unit.

should.be.mounted.away.from.noise.sensitive.spaces.and.must.

have.adequate.support.to.avoid.vibration.and.noise.transmission.

into.the.building ..Units.should.be.mounted.over.corridors,.utility.

areas,.rest.rooms.and.other.auxiliary.areas.where.high.levels.

of.sound.are.not.an.important.factor ...Sound.and.structural.

consultants.should.be.retained.for.recommendations .

Walls or Obstructions

The.unit.should.be.located.so.that.air.may.circulate.freely.and.not.

be.recirculated ..For.proper.air.flow.and.access.all.sides.of.the.unit.

should.be.a.minimum.of.“W”.away.from.any.wall.or.obstruction ..

It.is.preferred.that.this.distance.be.increased.whenever.

possible ..Care.should.be.taken.to.see.that.ample.room.is.left.for.

maintenance.work.through.access.doors.and.panels ..Overhead.

obstructions.are.not.permitted ...When.the.unit.is.in.an.area.where.

it.is.enclosed.by.three.walls.the.unit.must.be.installed.as.indicated.

for.units.in.a.pit .

Multiple Units

For.units.placed.side.by.side,.the.minimum.distance.between.

units.is.the.width.of.the.largest.unit ..If.units.are.placed.end.to.

end,.the.minimum.distance.between.units.is.4.feet .

Units in Pits

The.top.of.the.unit.should.be.level.with.the.top.of.the.pit,.and.

side.distance.increased.to.“2W” .
If.the.top.of.the.unit.is.not.level.with.the.top.of.pit,.discharge.

cones.or.stacks.must.be.used.to.raise.discharge.air.to.the.top.of.

the.pit ..This.is.a.minimum.requirement .

Decorative Fences

Fences.must.have.50%.free.area,.with.1.foot.undercut,.a.“W”.

minimum.clearance,.and.must.not.exceed.the.top.of.unit ....

If.these.requirements.are.not.met,.unit.must.be.installed.as.

indicated.for.“Units.in.pits” .

*..“W”.=.Total.width.of.the.condenser .