Electrical Wiring

The.electrical.installation.should.be.in.accordance.with.National.

Electrical.Code,.local.codes.and.regulations ..Proper.overcurrent.

protection.should.be.provided.for.the.fan.motors ..

.

All.standard.motors.have.internal.inherent.overload.protectors ..

Therefore,.contactors.can.be.used.instead.of.starters.requiring.

thermal.protectors,.eliminating.the.problem.of.furnishing.the.

proper.heating.elements ..

.

All.air-cooled.condensers.are.furnished.with.either.single-phase.

or.three-phase.fan.motors.which.are.identified.by.the.unit.

dataplate ..

.

Electrical.leads.from.each.motor.terminate.at.the.unit.junction.

box ..Field.connections.must.be.made.from.these.leads.in.

accordance.with.local,.state.and.national.codes ..

.

Three-phase.motors.must.be.connected.to.three-phase.power.of.

voltage.to.agree.with.motor.and.unit.dataplate ..

.

The.motors.are.wired.into.a.common.junction.box ..Where.

fan.cycling.is.furnished.and.factory.installed,.the.motors.are.

completely.wired.through.the.control.and.to.the.contactors ...The.

motors.must.be.checked.for.proper.rotation ..Be.sure.to.check.that.

motor.voltage.and.control.connection.agree.with.electric.services.

furnished .

Discharge Lines

The.proper.design.of.discharge.lines.involves.two.objectives:.

1 .. To.minimize.refrigerant.pressure.drop,.since.high.. .

pressure.losses.cause.increased.compressor..

.

.

horsepower.per.ton.of.refrigerant .

2 .. To.maintain.sufficiently.high.gas.velocity.to.carry.oil..

.

through.to.the.condenser.coil.and.receiver.at.all.loading..

.

conditions .

Table 2. Condensing Temperature Correction Factor

Condensing

Temperature

Discharge Line

R-22

R-502

R-404A

R-507

R-407C

R-410A

R-134A

90

0 .88

0 .91

0 .922

0 .924

0 .872

0 .889

0 .882

100

0 .95

0 .97

0 .974

0 .975

0 .957

0 .963

0 .961

110

1 .04

1 .02

1 .009

1 .005

1 .036

1 .032

1 .026

120

1 .10

1 .08

1 .026

1 .014

1 .009

1 .096

1 .078

130

1 .18

1 .16

1 .043

1 .024

1 .182

1 .160

1 .156

Table 1. Tons of Refrigeration

Line Size

Type L Copper

OD

Discharge Line

Drain Line

Velocity 100 FPM Refrigerant

R-22 Sat. Suction Temp (°F)

R-404A/R-507 Sat. Suction Temp (°F)

-40

0

40

-40

0

40

R-22

R-404A

1/2

0 .75

0 .8

0 .85

0 .56

0 .63

0 .7

2 .3

1 .5

5/8

1 .4

1 .5

1 .6

1 .0

1 .2

1 .3

3 .7

2 .3

7/8

3 .7

4 .0

4 .2

2 .7

3 .1

3 .4

7 .8

4 .9

1-1/8.

7 .5

8 .0

8 .5

5 .5

6 .3

7 .0

13 .2

8 .3

1-3/8

13 .1

14 .0

14 .8

9 .6

10 .9

12 .1

20 .2

12 .6

1-5/8

20 .7

22 .0

23 .4

15 .2

17 .2

19 .1

28 .5

17 .9

2-1/8

42 .8

45 .7

48 .5

31 .4

35 .6

39 .5

49 .6

31 .1

2-5/8

75 .4

80 .4

85 .4

55 .3

62 .8

69 .5

76 .5

48 .0

3-1/8

120 .2

128 .2

136 .2

87 .9

99 .8

110 .5

109 .2

68 .4

3-5/8

178 .4

190 .3

202 .1

130 .5

148 .1

164 .0

147 .8

92 .6

4-1/8

251 .1

267 .8

284 .4

183 .7

208 .4

230 .9

192 .1

120 .3

Source:..ASHRAE.Refrigeration.Handbook:

1 .. Line.sizes.based.on.pressure.drop.equivalent.to.1°F.per.100.equivalent.feet .

2 .. Values.in.Table.are.based.on.105°F.condensing.temperature ...Multiply.Table.capacities.by.the.factors.in.Table.2.for.other.condensing.temperatures .

3 .. If.subcooling.is.substantial.or.the.line.is.short,.a.smaller.line.size.may.be.used ..Applications.with.very.little.subcooling.or.very.long.lines.may.require.larger.sizes