Typical Arrangements

Figure.1.illustrates.a.typical.piping.arrangement.involving.a.

remote.condenser.located.at.a.higher.elevation,.as.commonly.

encountered.when.the.condenser.is.on.a.roof.and.the.compressor.

and.receiver.are.on.grade.level.or.in.a.basement.equipment.

room ..

.

In.this.case,.the.design.of.the.discharge.line.is.very.critical ...If.

properly.sized.for.full.load.condition,.the.gas.velocity.might.be.

too.low.at.reduced.loads.to.carry.oil.up.through.the.discharge.

line.and.condenser.coil ..Reducing.the.discharge.line.size.would.

increase.the.gas.velocity.sufficiently.at.reduced.load.conditions;.

however,.when.operating.at.full.load,.the.line.would.be.greatly.

undersized,.and.thereby.create.an.excessive.refrigerant.pressure.

drop ..This.condition.can.be.overcome.in.one.of.two.following.

ways:.

.

. 1 ..The.discharge.line.may.be.properly.sized.for.the.desired..

. . pressure.drop.at.full.load.conditions.and.an.oil.separator.

. . installed.at.the.bottom.of.the.trap.in.the.discharge.line.

. . from.the.compressor ..

.

. 2 ..A.double.riser.discharge.line.may.be.used.as.shown.in.

. . Figure.2 ..Line.“A”.should.be.sized.to.carry.the.oil.at.minimum..

. . load.conditions.and.the.line.“B”.should.be.sized.so.

. . that.at.the.full.load.conditions.both.lines.would.have..

. . sufficient.flow.velocity.to.carry.the.oil.to.the.condenser ..

.

For.more.complete.information,.refer.to.the.ASHRAE.Handbook.

on.Systems .

Figure 1

Figure 2

Notes:

1 .. All.oil.traps.are.to.be.as.short.in.radius.as..

.

.

possible ..Common.practice.is.to.fabricate.the..

.

.

trap.using.three.90.degrees.ells ..

2 .. Pressure.relief.valves.are.recommended.at.the..

.

.

condenser.for.protection.of.the.coil ..

.

3 .. A.drain.line.check.valve.is.recommended.for..

.

.

applications.where.the.condenser.may.be.at.a..

.

.

lower.temperature.than.the.receiver .

Installation, Refrigerant Piping

Install.piping.according.to.standard.accepted.refrigeration.

practice ..The.following.recommendations.should.be.adhered.to:.

.

1 .. See.Tables.1.and.2.for.discharge.and.liquid..

.

.

.

drain.line.sizes.for.remote.condenser..

.

.

connections ..

.

.

2 .. Use.only.refrigeration.grade.copper.tubing ..

.

.

3 .. Soft.solder.joints.are.not.acceptable ..

.

.

4 .. Put.dry.nitrogen.through.lines.while.brazing ..

.

.

5 .. Do.not.leave.dehydrated.piping.or.components.

.

.

open.to.the.atmosphere.any.longer.than.is.

.

.

absolutely.necessary ..