Heatcraft Refrigeration Products Air-Cooled Condensers none User Manual
Page 13
13
Table 9. Flooded Charge Temperature Difference Factor
Ambient, °F
Design T.D.
30
25
20
15
10
+60
–
0 .38
1 .0
1 .74
2 .46
+40
0 .59
0 .80
1 .0
1 .19
1 .40
+20
0 .76
0 .88
1 .0
1 .13
1 .25
0
0 .84
0 .91
1 .0
1 .07
1 .16
-20
0 .88
0 .93
1 .0
1 .05
1 .13
Table 10. Model Cross Reference
Model Reference
*NH
*NL
*NX
*NQ
*NE
1
*NH-S01-A007
*NL-S01-A007
*NX-S01-A006
*NQ-S01-A005
*NE-S01-A008
2
*NH-S01-A009
*NL-S01-A008
*NX-S01-A008
*NQ-S01-A006
*NE-S01-A009
3
*NH-S02-A011
*NL-S02-A010
*NX-S02-A010
*NQ-S02-A008
*NE-S02-A011
4
*NH-S02-A015
*NL-S02-A014
*NX-S02-A013
*NQ-S02-A010
*NE-S02-A015
5
*NH-S02-A017
*NL-S02-A016
*NX-S02-A015
*NQ-S02-A012
*NE-S02-A018
6
*NH-S03-A022
*NL-S03-A021
*NX-S03-A020
*NQ-S03-A016
*NE-S03-A023
7
*NH-S03-A026
*NL-S03-A024
*NX-S03-A023
*NQ-S03-A017
*NE-S03-A027
8
*NH-S04-A030
*NL-S04-A028
*NX-S04-A026
*NQ-S04-A021
*NE-S04-A031
9
*NH-S04-A034
*NL-S04-A032
*NX-S04-A030
*NQ-S04-A023
*NE-S04-A036
10
*NH-S05-A037
*NL-S05-A036
*NX-S05-A033
*NQ-S05-A026
*NE-S05-A039
11
*NH-S05-A044
*NL-S05-A042
*NX-S05-A038
*NQ-S05-A029
*NE-S05-A047
12
*NH-S06-A053
*NL-S06-A050
*NX-S06-A045
*NQ-S06-A034
*NE-S06-A056
13
*NH-S07-A061
*NL-S07-A055
*NX-S07-A052
*NQ-S07-A042
*NE-S07-A065
14
*NH-D04-A021
*NL-D04-A020
*NX-D04-A020
*NQ-D04-A016
*NE-D04-A023
15
*NH-D04-A029
*NL-D04-A028
*NX-D04-A026
*NQ-D04-A021
*NE-D04-A031
16
*NH-D04-A034
*NL-D04-A032
*NX-D04-A030
*NQ-D04-A023
*NE-D04-A036
17
*NH-D06-A044
*NL-D06-A042
*NX-D06-A040
*NQ-D06-A031
*NE-D06-A046
18
*NH-D06-A051
*NL-D06-A048
*NX-D06-A045
*NQ-D06-A034
*NE-D06-A054
19
*NH-D08-A058
*NL-D08-A056
*NX-D08-A053
*NQ-D08-A041
*NE-D08-A062
20
*NH-D08-A068
*NL-D08-A065
*NX-D08-A061
*NQ-D08-A046
*NE-D08-A073
21
*NH-D10-A074
*NL-D10-A071
*NX-D10-A066
*NQ-D10-A052
*NE-D10-A079
22
*NH-D10-A088
*NL-D10-A083
*NX-D10-A076
*NQ-D10-A057
*NE-D10-A093
23
*NH-D12-A106
*NL-D12-A100
*NX-D12-A091
*NQ-D12-A069
*NE-D12-A112
24
*NH-D14-A123
*NL-D14-A110
*NX-D14-A104
*NQ-D14-A083
*NE-D14-A129
*.First.letter.of.model.corresponds.to.a.particular.brand ..B.is.Bohn ..L.is.Larkin ..C.is.Climate.Control ..H.is.Chandler .
Maintenance
.
.
Air-cooled.condensing.units.require.a.minimum.of.maintenance ..
The.unit.coil.will.require.a.periodic.cleaning.and.this.can.be.
accomplished.by.a.brush,.vacuum.cleaner,.pressurized.air.
stream.or.a.commercially.available.coil.cleaning.foam ..All.of.
Cleaning Instructions
.
.
Heatcraft.recommends.that.the.finned.surface.of.this.unit.be.
cleaned.approximately.every.six.months;.more.frequent.cleaning.
may.be.required.if.extreme.conditions.cause.clogging.or.fouling.
of.air.passages.through.the.finned.surface ..
.
Calgon. Corporation's. CalClean. 41352. (or. equal). should. be.
acceptable. for. cleaning. this. unit .. CalClean. should. be. . applied.
liberally.to.entering.air.and.leaving.air.surfaces.of.the.finned.area.
in.accordance.with.the.label.directions .
the.condenser.fan.motors.have.sealed.ball.bearings ..The.only.
acceptable.service.to.these.bearings.is.replacement .
CAUTION:
Under.no.circumstances.should.this.unit.be.cleaned.with.an.acid-based.cleaner .