Start-Up

Check.for.proper.fan.rotation ...Air.is.drawn.through.the.coil.on.all.

units ...Be.sure.the.fans.turn.freely ..

.

Rotation.of.the.motors.and.blades.should.be.in.a.“CW”.direction.

looking.at.the.unit.from.the.blade.side ...On.three.phase.units,.it.

may.be.necessary.to.reverse.two.of.the.three.power.leads.to.the.

unit .

NOTE:

The manifold assembly is not designed to

support field piping. Any damages to the

condenser due to excessive weight,

pressure or vibration will not be covered

by our standard warranty.

Discharge Gas Pulsation

Gas.pulsations.in.a.refrigeration.system.are.most.commonly.

associated.with.the.compressor.and.connecting.discharge.

piping ..Variations.in.the.system.piping.configuration,.line.sizing,.

operating.pressures.and.compressor.and.component.mounting.

all.contribute.to.the.presence.and.magnitude.of.these.pulsations ..

.

The.vibration.and.movement.of.components.caused.by.the.

pulsations.may.result.in.line.breakage.or.damage.to.the.

condenser ..In.order.to.eliminate.discharge.pulsations.and.the.

potential.for.related.condenser.damage,.it.is.recommended.

that.a.discharge.muffler.be.installed.in.the.refrigeration.

piping ...In.all.cases,.the.recommendations.of.the.compressor.or.

muffler.manufacturer.must.be.followed.when.selecting.these.

components .

Fan Cycling

A.decrease.in.ambient.air.temperature.results.in.a.capacity.

increase.in.the.air-cooled.condenser ..This.capacity.increase.is.

directly.proportional.to.the.temperature.difference.between.the.

condensing.temperature.and.the.temperature.of.the.ambient.

air.entering.the.condenser ..Since.air-cooled.condensers.are.

often.required.to.operate.over.a.wide.range.of.ambient.air.

temperatures.and.variable.loading.conditions,.provisions.must.

be.made.to.maintain.the.overall.system.balance ..Any.air-cooled.

condenser.tends.to.run.at.a.low.head.pressure.when.operating.in.

a.low.ambient.air.temperature ..Low.head.pressures.could.result.in.

poor.expansion.valve.operation.and.poor.system.operation ..

.

The.cycling.of.condenser.fans.provides.an.automatic.means.of.

maintaining.head.pressure.control,.within.reasonable.limits,.at.

lower.ambient.air.temperatures ..A.fan.cycling.control.system.

allows.fans.to.cycle.in.sequence.by.sensing.either.ambient.

temperature.or.condensing.pressures ..However,.care.must.

be.used.by.the.engineer.or.installing.contractor.in.making.

adjustments.to.prevent.short.cycling.of.the.fan.motors ..Short.

cycling.is.normally.caused.by.too.close.a.differential.in.the.control.

settings.or.set.points ..If.flooding.valves.are.used.with.fan.cycling,.

they.must.be.set.to.follow.the.fan.cycling ..

.

Recommended.differential.settings.for.ambient.sensing.

thermostats.are.5°.F.and.a.minimum.of.35.PSIG.differential.for.

pressure.switches ..However,.system.or.climate.conditions.vary.

and.the.controls.may.require.further.field.adjustment.to.provide.

optimum.system.performance.and.prevent.short.cycling ..

.

Any.fan.cycle.that.is.less.than.three.minutes.is.considered.short.

cycling,.and.could.be.detrimental.to.the.system ..Adjust.controls.

accordingly ..It.is.also.recommended.that.the.fan.closest.to.the.

header.end.of.the.condenser.be.wired.to.run.continuously,.

whenever.the.compressor(s).is.(are).operational ..Cycling.all.of.

the.fans.off.usually.results.in.rapid,.short.cycling.of.the.fans.and.

erratic.head.pressure.control ..

.

If.additional.head.pressure.control.is.necessary.beyond.letting.the.

lead.fan.run,.we.recommend.adding.variable.speed.or.flooding.

controls ..If.cycling.the.header.fan.is.necessary.for.adequate.head.

pressure.control,.we.recommend.cycling.on.pressure ...Ambient.

sensing.thermostats.should.never.be.used.to.cycle.the.lead.fan ..

.

Fans.must.not.cycle.in.multiples.except.on.double.wide.single.

circuit.condensers.where.they.may.cycle.in.pairs.(one.motor.on.

each.side) ..Do.not.cycle.more.than.two.fans.at.a.time.on.double.

wide.condensers.and.only.one.fan.at.a.time.on.single.wide.

condensers .

Operation

Winter Operation Head Pressure Control

The.capacity.of.an.air-cooled.condenser.varies.with.the.difference.

between.the.entering.air.dry.bulb.temperature.and.the.

condensing.temperature.of.the.refrigerant ...Since.air.temperature.

in.some.regions.varies.as.much.as.100°.from.summer.to.winter,.

some.means.must.be.employed.to.keep.the.condensing.

temperature.sufficiently.high.to.insure.proper.operation.of.the.

refrigerant.expansion.valve.during.low.ambient.operation,.and.

also.allow.sufficient.capacity.so.that.excessively.high.condensing.

temperatures.do.not.result.during.high.ambient.conditions ..

.

The.low.limit.of.the.head.pressure.is.dependent.upon.the.

required.pressure.drop.across.the.thermostatic.expansion.valve ...

For.normal.air.conditioning.applications,.head.pressure.should.

be.maintained.above.a.condensing.temperature.corresponding.

to.90°.F ..This,.in.effect,.corresponds.to.a.normal.lower.limit.of.

about.60°.F.ambient.air ..Since.air.conditioning.is.not.normally.

required.at.these.lower.ambient.temperatures,.condenser.head.

pressure.control.may.not.always.be.necessary ..However.for.those.

applications.which.are.of.such.a.nature.that.operation.is.required.

below.60°.F.ambient.air.temperature,.additional.head.pressure.

control.will.be.required .