Inspection

Responsibility.should.be.assigned.to.a.dependable.individual.at.

the.job.site.to.receive.material ..Each.shipment.should.be.carefully.

checked.against.the.bill.of.lading ..The.shipping.receipt.should.

not.be.signed.until.all.items.listed.on.the.bill.of.lading.have.been.

accounted.for ..

.

Check.carefully.for.concealed.damage ..Any.shortage.or.damages.

should.be.reported.to.the.delivering.carrier ..

.

Damaged.material.becomes.the.delivering.carrier's.responsibility,.

and.should.not.be.returned.to.the.manufacturer.unless.prior.

approval.is.given.to.do.so ..When.uncrating,.care.should.be.taken.

to.prevent.damage ..Heavy.equipment.should.be.left.on.units.

shipping.base.until.it.has.been.moved.to.the.final.location ..

.

.

System Warranty

This.equipment.is.designed.to.operate.properly.and.produce.

rated.capacity.when.installed.in.accordance.with.accepted.

industry.standards ..Failure.to.meet.the.following.conditions.may.

result.in.voiding.of.the.system.warranty:

.

1 .. System.piping.must.be.installed.following.industry..

.

.

standards.for.good.piping.practices ..

.

.

2 .. Inert.gas.must.be.charged.into.piping.during..welding ..

.

.

3 .. System.must.be.thoroughly.leak.checked.and.. .

.

.

evacuated.before.initial.charging ..High.vacuum.

.

.

gauge.capable.of.. reading.microns.is.mandatory ...

.

.

Dial.indicating.pressure.gauges.are.not.acceptable ..

.

.

4 .. Power.supply.to.system.must.meet.the..

.

.

following.conditions:

.

.

a .. Voltage.for.208/230.motors.not.less.than..

.

.

.

195.volts.or.more.than.253.volts .

.

.

b .. All.other.voltages.must.not.exceed.+/-.10%..

.

.

.

of.nameplate.ratings .

.

.

c .. Phase.imbalance.not.to.exceed.2% .

.

5 .. All.controls.and.safety.switch.circuits.properly.

.

.

connected.per.wiring.diagram .

.

6 .. Factory.installed.wiring.must.not.be.changed.without..

.

.

written.factory.approval ..

.

Installation

Note:

Installation and maintenance to be performed

only by qualified personnel who are familiar with

local codes and regulations, and experienced

with this type of equipment.

Caution: Sharp edges and coil surfaces are a potential injury

hazard. Avoid contact with them.

Unit Location

Units.are.designed.for.outdoor.application.and.may.be.mounted.

on.a.roof.or.concrete.slab.(ground.level.installation) ...Roof.

mounted.units.should.be.installed.level.on.steel.channels.or.an.

I-beam.frame.to.support.the.unit.above.the.roof ..Use.of.vibration.

pads.or.isolators.is.recommended ..The.roof.must.be.strong.

enough.to.support.the.weight.of.the.unit ...Concrete.slabs.used.

for.unit.mounting.should.be.installed.level.and.be.properly.

supported.to.prevent.settling ..A.one-piece.concrete.slab.with.

footings.extending.below.the.frost.line.is.recommended ..

.

The.condenser.should.be.located.far.enough.away.from.any.

wall.or.other.obstruction.to.provide.sufficient.clearance.for.air.

entrance ..Do.not.attach.ductwork.to.the.coil.inlet.or.fan.outlet ...

Care.should.be.taken.to.avoid.air.recirculation.conditions.that.

can.be.caused.by.sight.screening,.walls,.etc ..Also.keep.unit.fan.

discharge.away.from.any.building.air.intakes ..See.page.4.for.

space.and.location.requirements ..

.

Sound Vibration

Units.should.be.installed.away.from.occupied.spaces.and.above.

or.outside.of.utility.areas,.corridors.and.auxiliary.spaces.to.reduce.

the.transmission.of.sound.and.vibration.to.occupied.spaces ..

The.refrigerant.piping.should.be.flexible.enough.to.prevent.

the.transmission.of.noise.and.vibration.from.the.unit.into.the.

building ..If.the.refrigerant.lines.are.to.be.suspended.from.the.

structure.of.the.building,.isolation.hangers.should.be.used.to.

prevent.the.transmission.of.vibration ..Where.piping.passes.

through.a.wall,.it.is.advisable.to.pack.fiberglass.and.sealing.

compound.around.the.lines.to.minimize.vibration.and.retain.

flexibility.in.the.lines ..

.

The.unit.needs.to.be.secured.in.its.final.location ..Holes.are.

provided.in.the.base.runner.for.this.purpose .

Warning:

This equipment may contain a substance

which harms the public health and

environment by destroying ozone in the

upper atmosphere. Venting of certain

refrigerants to the atmosphere is illegal.

Refrigerant recovery devices must be used

when installing or servicing this product.

Consult your local codes for requirements

in your location.

Warning:

There may be more than one source of

electrical current in this unit. Do not

service before disconnecting all power

supplies.