Master/Slave Configuration

The.EC.motor.control.signals.are.wired.in.a.Master/

Slave.configuration ...This.configuration.allows.for.the.

maximum.sound.and.energy.reduction.as.well.as.the.

most.stable.head.pressure.control ...The.control.signal.is.

delivered.to.the.master.motor.(located.at.the.header.end.

of.the.unit) ...The.master.motor.relays.the.control.signal.to.

the.adjacent.slave.motor ...This.relay.is.done.until.the.last.

motor.is.reached ...As.each.slave.relays.the.control.signal,.

it.adjusts.the.signal.so.the.next.slave.will.run.slightly.

slower.than.the.upstream.motor ...The.end.result.of.this.is.

that.when.a.motor.receives.a.small.enough.signal,.it.will.

turn.off ...This.provides.built-in.fan.cycling .

Protective Features

The.EC.motors.have.many.built-in.protective.features .

The.EC.motors.have.functions.within.the.motor.to.

protect.against:

•.over-temperature.of.electronics

•.over-temperature.of.motor

•.incorrect.rotor.position.detection

With.any.of.these.failures,.the.motor.stops.electronically.

and.the.alarm.relay.is.switched ...With.one.of.these.

failures,.the..motor.WILL.NOT.automatically.restart ...To.

reset,.the.power.supply.has.to.be.switched.off.for.a.

minimum.20.seconds.once.the.motor.is.at.standstill .

Locked-rotor protection

As.soon.as.the.rotor.is.blocked,.the.motor.gets.switched.

off.electronically.and.the.alarm.relay.is.switched ..After.

de-blocking,.the.motor.WILL.restart.automatically .

Under-voltage protection

If.power.supply.voltage.falls.below.~150VAC/3Ø.(for.230V.

motors).or.~290VAC/3Ø.(for.460V.motors).for.5.seconds.

minimum,.the.motor.will.be.switched.off.electronically.

and.the.alarm.relay.is.switched ...If.power.supply.

voltage.returns.to.correct.values,.the.motor.WILL.restart.

automatically .

Phase failure

If.1.phase.fails.for.5.seconds.minimum,.the.motor.will.

be.switched.off.electronically.and.the.alarm.relay.is.

switched ...If.all.3.phases.return.to.correct.values,.the.

motor.WILL.restart.automatically.within.10-40.seconds .

EC Motor Wiring

All.EC.motor.wiring.is.done.at.the.factory ...If.any.motor.

wiring.needs.to.be.done.in.the.field,.the.diagram.below.

indicates.the.terminal.pin.configurations.inside.the.

motor.junction.box ..Terminals.in.shaded.area.are.not.

normally.used .

The.following.diagram.shows.typical.motor.wiring.for.a.1.

x.4.EC.condenser .