5. CONFIGURING THE SCHEDULE

Use this page to configure the schedule events and holidays to be used by the Stryker VAV device. You can also configure

occupancy override related parameters in this page.

To set schedule:

5.1 Fields

Table 6. Schedule Fields.

RELATED TOPICS

“1. About Stryker VAV” on page 2

“2. Configuration” on page 4

Step

Action

1

From the left pane of the

VAV Configuration Wizard, select Schedule.

2

Select the

Local Schedule Type from the drop-down list. The available options are Default Occupied, Default

unoccupied and Custom Schedule.

3

Select

Custom Schedule to add events. You can add maximum four events in a day.

4

Click the

Holiday tab to configure holidays.

5

Enter information in the available fields.

6

Click

Next to display the PID page.

7

Click

Undo All to revert to the last saved settings.

8

Click

Finish to save settings to station.

Name

Definition

Local Schedule Type

The local schedule object present in the Stryker VAV device can be configured as one of three types

supported:

Default Occupied, Default Unoccupied or Custom Schedule.

Apply Event

Enables you to customize the schedule by adding or editing the events for the selected day. A

maximum of 4 events can be configured per day. Events can be configured as Occupied, Unoccupied,

No events or Standby.

Import Schedule

Enables you to import the schedule settings from external files. You can reuse the preconfigured

schedule settings.

Export Schedule

Enables you to export the schedule settings to external files.

Override Button

Behavior

Enables you to select the override behavior such as Not used, Connected with full use and Connected

for bypass options only.

NOTE: This field is configurable only when the Wall Module type selected is Conventional

wall module and the Override input is configured.

Override Duration

Enables you to enter the override duration. The time range is 0 to 1092 minutes.

Standby Mode

Operation

Enables you to select the standby mode operation such as Unoccupied for the fan and auxiliary output

and Occupied for the fan and auxiliary output.

Holiday Type

There are two types of holidays: Weekday/Month every year, and Specific date every year.

Configure Holiday

Enables you to configure holidays by setting months, weekdays and total duration of days. You can

add US, European, and Canadian holidays as well.

Holiday List

Displays the list of holidays after configuration. You can add upto 10 declared holidays in list.

Import Holiday

Enables you to import the holiday settings from an external file.

Export Holiday

Enables you to save the holiday settings in an external file.