16. SENSOR CALIBRATION

Use this page for sensor calibration in an Stryker VAV device on the LON network. Using Sensor Calibration feature, you can

correct the input values to the controller. This action can be performed with the device in online mode. The controller must be in a

commissioned state. While performing Sensor Calibration, the device should not be used by another application. You can

calibrate only analog inputs to the controllers.

To calibrate:

16.1 Fields

Table 15. Sensor Calibration Fields.

Tip

To clear the Offset value for any of the configured

sensors:

Calculate the calibrated value using the below formula, type it

in the Calibrated value field and click Calibrate.

Calibrated Value = Actual Value - Old Offset Value

For Example:

If the configured Sylk bus sensor reads the room temperature

as 79.88 F and you want to calibrate it to 85.5 F. By mistake if

you type the calibrated value as 855 F, the offset value will be

calculated as 775.102 F. This will display the Actual value as -

324.742 which is abnormal.

If you find any abnormal value like this and you want to clear

the offset value. Calculate the Calibrated value as shown

below and type the calculated value in the Calibrated Value

field.

In this case

The Actual value = -324.742

Old Offset value = 775.102

Calibrated Value = Actual Value - Old Offset Value

= -324.742-775.102

= -1099.844 F

If you type this value in the Calibrated Value field and click

Calibrate, the Offset value will be cleared.

RELATED TOPICS

“1. About Stryker VAV” on page 2

“2. Configuration” on page 4

Step

Action

1

From the

Nav menu, choose Station > Driver > LON network > AscLonVAV device.

2

Right-click the device and choose

Views > Sensor Calibration from device items. The Sensor

Calibration screen appears.

3

Enter information in the available fields.

4

Click

Refresh to refresh the settings.

5

Click

Calibrate to calibrate settings.

Name

Definition

Sensor Name

Displays the sensor names.

Actual Value

Displays the current value of the sensor as read by the controller.

Calibrated Value

Enter the calibrated value.

Offset Value

Once you click

Calibrate, the offset value appears. Offset value is a difference between

Actual value and Calibrated value.