Configuration, 1 adding a device, 2 configuring the stryker vav device – Honeywell Stryker VAV 62-2030-01 User Manual

Page 4: 3 fields

Advertising
background image

STRYKER VAV USER GUIDE

62-2030—01

4

2. CONFIGURATION

2.1 Adding a device

Use this page to add an Stryker VAV device to the LON network. You can add a device either in the online mode or the offline

mode.

To add an Stryker VAV device:

2.2 Configuring the Stryker VAV Device

Use this page to configure an Stryker VAV device on the LON network. You can configure the device either in the online mode or

the offline mode.

To configure the Stryker VAV device:

2.3 Fields

Step

Action

1

From the Lon Device Manager, click New. The New dialog box appears.

2

Select AscLonVAV Device from the Type to Add list.

3

Type one in the Number to Add box. Click Ok. The details of the device are displayed.

4

Enter information in the available fields.

5

Click Ok. You can view the newly added device under Local Lon Device items in the Nav palette.
Note: The other way to add a new device is by using the Lon Discover option.

Step

Action

1

From the

Nav menu, choose Station > Driver > LON network > AscLonVAV device.

2

Double click

AscLonVAVDevice. The VAV Configuration Wizard page appears.

3

Enter information in the available fields.

4

Click

Next to display the Outputs page.

5

Click

UndoAll to revert to the last saved settings.

6

Click

Finish to save settings to station.

Table 3. Stryker VAV Device Fields.

Name

Definition

Controller Type

Displays the Controller Type such as With Actuator or Without Actuator.

Pressure Type

Displays the VAV Terminal Unit pressure control operation for this application. This selection defines

how the controller will operate the VAV Terminal Units damper. Valid selections for this field are:

Pressure Independent - The controller uses airflow as the primary means of controlling the VAV

Terminal Damper.

Pressure Dependent - The controller uses space temperature as the primary means of controlling

the VAV Terminal Damper.

Box Type

Displays the physical type of VAV Terminal. This selection determines what control options are

available for the VAV Terminal. Valid selections for this field are:

Single Duct: This VAV Terminal type consists of a single primary air supply inlet connection with or

without a primary flow sensor. This box type is primarily used for cooling only applications, cooling

with local reheat or dual temperature (central heating/cooling) systems.

Advertising