Heat & Glo • Escape-42DV • 2052-900 Rev. R • 10/08

26

SCREWS

CAULK

STORM
COLLAR

(1 of 3)

D. Installing Roof Flashing and

Vertical Termination Cap

To install roof fl ashing see Figure 8.13.

For installation of vertical termination cap see minimum
vent heights for various pitched roofs (see Figure 8.13).

Caulk the gap between the roof fl ashing and the outside
diameter of the pipe. Also caulk the perimeter of fl ashing
that contacts roof surface as shown in Figure 8.15.

To attach the vertical termination cap, slide the inner col-
lar of the cap into the inner fl ue of the pipe section and
place the outer collar of the cap over the outer fl ue of the
pipe section.

Secure with three screws into the outer fl ue. Secure the cap
by driving the three self-tapping screws (supplied) through
the pilot holes in the outer collar of the cap into the outer
fl ue of the pipe (see Figure 8.14).

Roof Pitch H (Min.) Ft.

Flat to 6/12....................................... 1.0*

Over 6/12 to 7/12 ........................... 1.25*

Over 7/12 to 8/12 ............................. 1.5*

Over 8/12 to 9/12 ............................. 2.0*

Over 9/12 to 10/12 ............................ 2.5

Over 10/12 to 11/12 ........................ 3.25

Over 11/12 to 12/12 .......................... 4.0

Over 12/12 to 14/12 .......................... 5.0

Over 14/12 to 16/12 .......................... 6.0

Over 16/12 to 18/12 .......................... 7.0

Over 18/12 to 20/12 .......................... 7.5

Over 20/12 to 21/12 .......................... 8.0

* 3 foot minimum in snow regions

Figure 8.13 Minimum height from roof to lowest discharge

opening

Fire Risk.

Explosion Risk.

Inspect external vent cap regularly.

• Ensure no debris blocks cap.

• Combustible materials blocking cap may

ignite.

• Restricted air fl ow affects burner operation.

HORIZONTAL

OVERHANG

VERTICAL

WALL

GAS DIRECT VENT
TERMINATION CAP

12

X

ROOF PITCH

IS X/ 12

LOWEST

DISCHARGE

OPENING

2 FT.

MIN.

20 INCHES MIN.

H (MIN.) - MINIMUM HEIGHT FROM ROOF
TO LOWEST DISCHARGE OPENING

Figure 8.14

WARNING

Figure 8.15

TERMINATION CAP

CAULK