CHECKING GAS CONNECTIONS

WARNING: Test all gas pip-

ing and connections, internal

and external to unit, for leaks

after installing or servicing. Cor-

rect all leaks at once.

WARNING: Never use an

open flame to check for a leak.

Apply a noncorrosive leak

detection fluid to all joints.

Bubbles forming show a leak.

Correct all leaks at once.

CAUTION: Make sure exter-

nal regulator has been installed

between propane/LP supply and

fireplace. See guidelines under

Connecting Fireplace to Gas

Supply, page 15.

PRESSURE TESTING GAS SUPPLY

PIPING SYSTEM
Test Pressures In Excess Of 1/2 PSIG

(3.5 kPa)

1. Disconnect fireplace with its main gas

valve (control valve) and equipment shut-

off valve from gas supply piping system.

Pressures in excess of 1/2 psig will dam-

age fireplace regulator.

2. Cap off open end of gas pipe where equip-

ment shutoff valve was connected.

3. Pressurize supply piping system by either

opening propane/LP supply tank valve

for propane/LP gas or opening main gas

valve located on or near gas meter for

natural gas or using compressed air.

4. Check all joints of gas supply piping system.

Apply noncorrosive leak detection fluid to all

joints. Bubbles forming show a leak.

5. Correct all leaks at once.
6. Reconnect fireplace and equipment

shutoff valve to gas supply. Check recon-

nected fittings for leaks.

INSTALLATION

Continued

Figure 18 - Equipment Shutoff Valve

Open

Closed

Equipment

Shutoff Valve

Figure 20 - Checking Gas Joints for

Propane/LP Gas

Propane/LP

Supply Tank

Equipment

Shutoff

Valve

Gas Control Valve

Gas Meter

Figure 19 - Checking Gas Joints for

Natural Gas

Gas Control Valve

Equipment Shutoff Valve

Test Pressures Equal To or Less Than

1/2 PSIG (3.5 kPa)

1. Close equipment shutoff valve (see

Figure 18).

2. Pressurize supply piping system by either

opening propane/LP supply tank valve

for propane/LP gas or opening main gas

valve located on or near gas meter for

natural gas or using compressed air.

3. Check all joints from gas meter to equip-

ment shutoff valve for natural gas or pro-

pane/LP supply to equipment shutoff valve

for propane/LP (see Figures 19 and 20).

Apply noncorrosive leak detection fluid to

all joints. Bubbles forming show a leak.

4. Correct all leaks at once.