Model fc150erv, Performance, Dimensions fc150erv – Field Controls Heat Recovery Ventilator FC95HRV. User Manual

Page 12: 75 lbs. (34kg), Weight, Shipping weight

Advertising
background image

12

STALE AIR

TO OUTSIDE

FRESH AIR

FROM OUTSIDE

STALE AIR

FROM INSIDE

FRESH AIR

TO INSIDE

14

3

/

4

"

(375)

1

9

"

(4

8

3

)

*

All Duct Connections 6"(150mm)

FILTERS

BLOWERS

*NOTE: Front clearance
of 25 inches (635 mm)

is recommended

for servicing unit.

MOTOR

ENTHALPIC CORE

33-5/8"

(850)

BALANCING

DAMPER

BALANCING

DAMPER

CORE

Model FC150ERV

DIMENSIONS FC150ERV

inches (mm)

Date: ___________________________________________
Tag: _____________________Qty:___________________
Project: _________________________________________
Engineer: _______________________________________

Contractor: ______________________________________
Supplier: ________________________________________
Quote#: _________________________________________
Submitted by: ____________________________________

All units conform to CSA and UL

standards.

Static Pressure (in w.g.)

A

ir

Fl

ow

(c

fm

)

20

40

60

80

100

120

140

160

180

200

220

0

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

1 - Low speed

2 - High Speed

2

1

*Sensible Efficiency – thermal **Latent Efficiency – moisture

Note: Effectiveness - based on temp. differential between the 2 airstreams

Efficiency – takes into account all power inputs

Performance

Net supply air flow in cfm (L/s) against external static pressure

E.S.P

(external static pressure)

[cfm (L/s)]

@ 0.1" (25 Pa)

151 (71)

@ 0.2" (50 Pa)

140 (66)

@ 0.3" (75 Pa)

131 (62)

@ 0.4" (100 Pa)

123 (58)

@ 0.5" (125 Pa)

107 (50)

@ 0.6" (150 Pa)

98 (46)

@ 0.7" (175 Pa)

81 (38)

@0.8 " (200 Pa)

60 (28)

Sensible Effectiveness
@ 64 cfm (30 L/s)

32°F (0°C)

81%

*Sensible Efficiency
@ 64 cfm (30 L/s)

32°F (0°C)

69%

Total Efficiency

50%

@ 64 cfm (30L/s)

95°F (35°C)

47%

VAC @ 60HZ

120

WATTS / Low speed.

63

WATTS / High speed

173

Amp rating

1.4

LATENT RECOVERY/MOISTURE TRANSFER CORE

The cross-flow energy recovery core transfers heat and water vapor

between the two airstreams. It is easily removed for cleaning or service.

MOTORS AND BLOWERS

Each air stream has one centrifugal blower driven by a common PSC

motor. 5 speed fan operation.

FILTERS

Washable air filters in exhaust and supply air streams.

MOUNTING THE ERV

Four threaded inserts at corners of case designed to accept the "S" hooks

and hanging straps supplied with the unit.

CASE

Twenty gauge prepainted galvanized steel (G60) for superior corrosion

resistance. Insulated to prevent exterior condensation. Door balancing

ports.

WEIGHT

75 lbs. (34Kg)

SHIPPING WEIGHT

77lbs. (35Kg)

ELECTRONICS

•Built-in Relay for Interfacing to furnace

OPTIONAL CONTROLS

# DHVC Ventilation Control

• 2 Speed Fan setting (Low/High) • Dehumidistat

#HHSC

Healthy Home System Control

• Automatically activates the unit to deliver fresh air into your home

#DH1

Dehumidistat

• Initiates high speed ventilation when the indoor humidity level exceeds

the set point
OPTIONAL TIMERS

#VTC

Ventilation Timer Control - Initiates high speed ventilation

for 20, 40, or 60 minutes, (3 wire) 20 gauge wire (min.) 100'

length

OPTIONAL ACCESSORIES

#WH 186 Weatherhoods, Two - 6” (150 mm) c/w 1/4” (6 mm) mesh

screen

WARRANTY

Units carry a five (5) year warranty

on the enthalpic (ERV) core and a 5

year replacement parts warranty.

Advertising