Warning – Field Controls Heat Recovery Ventilator FC95HRV. User Manual

Page 14

Advertising
background image

DIRECT CONNECTION of both the HRV SUPPLY AIR STREAM and

EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN

Installation Notes

• Unit is normally balanced on HIGH speed with the furnace blower ON.

• A minimum separation of 40 inches (1m) is recommended between the

two direct connections.

• The exhaust air connection should be upstream of the supply air

connection to prevent exhausting any fresh air.

• Weatherhood arrangement is for drawing purposes only. Six feet (2m)

minimum separation is recommended. The Weatherhood must also be 18"

(460mm) above grade minimum.

• The airflow must be confirmed on site using the balancing procedures found in this manual

Spring-Loaded Backdraft Damper

Install the Backdraft Damper with the leaf hinge vertical.

The damper is installed on the “Stale Air to Outside Collar”.

4” (102mm) Backdraft Damper Part No. 99-RSK4

5” (127mm) Backdraft Damper Part No. 99-RSK5

6” (152mm) Backdraft Damper Part No. 99-RSK6

8” (203mm) Backdraft Damper Part No. 99-RSK8

The Stale Air to Outside air duct requires
a Backdraft Damper. This damper prevents
outdoor air from entering the HRV
during the operation of the Furnace/
Air Handler while the HRV is in standby,
OFF or Recirculate.

WARNING

RETURN AIR

40" (1m) MINIMUM

Outdoors

Cool Air

Return

3' min.

recommended

Forced Air

Furnace

Dampers for
balancing
airflows

Backdraft
Damper

Leaf Hinge

Simplified Installation Diagrams

Simplified Installation (Return/Return Method)

Key Points
• The HRV/ERV must be balanced.
• It is mandatory that the furnace blower run continuously or

HRV/ERV operation be interlocked with the furnace

blower. (Refer to “Interlocking the HRV/ERV to an Air

Handler/Furnace Blower.”)

• The duct configuration may change depending on the

HRV/ERV model. See specifications for your unit.

• Check local codes / authority having jurisdiction for

acceptance.

• A backdraft damper is required in the exhaust air duct to

prevent outdoor air from entering the unit when the

Furnace/Air Handler is running and the unit is in Standby,

OFF or Recirculate.

Sizing the Ductwork

It is the responsibility of the installer to ensure all ductwork is

sized and installed as designed to ensure the system will

perform as intended.
The amount of air (cfm) that an HRV/ERV will deliver is

directly related to the total external static pressure (E.S.P.) of

the system. Static pressure is a measure of resistance imposed

on the blower by length of duct work plus the number of

fittings used in the duct work.

DIRECT CONNECTION of the SUPPLY AIR STREAM and

EXHAUST AIR STREAM to the FURNACE COLD AIR RETURN.

14

(not included)

Advertising