Drain Connection (HRV only)

Grilles

Drain Connection

The HRV may produce some condensation during a defrost cycle.

This water should flow into a nearby drain, or be taken away by a

condensate pump.

The HRV cabinet has prepunched holes for the drain (see below).

Insert the drain spout through the hole in the drain pan. Be sure to

install the "O ring" which seals each spout to the pan. HAND

TIGHTEN the washer and lock nut which hold the drain spout in

place.
Construct a P-Trap using the plastic tee connector. Cut two lengths

of 1/2" drain hose (not included) and connect the other ends to the

two drain spouts. Position the "T" fitting to point upward and

connect the drain line. Tape or fasten base to avoid any kinks. Pour

a cup of water into the drain pan of the HRV after the drain

connection is complete. This creates a water seal which will

prevent odors from being drawn up the hose and into the fresh air

supply of the HRV.

Adjustable grilles should be used to balance the flow rates into and

out of various rooms. The grilles should not be adjusted after

balancing the unit.
Grilles or diffusers should be positioned high on the wall or in the

ceiling. Kitchen Exhaust grilles must never be connected to the

range hood. They should be installed at least 4 feet (1.2 m)

horizontally away from the stove.
Field supplied balancing dampers should be installed external to

the unit to balance the amount of stale air being exhausted with the

amount of fresh air being brought into the house. Refer to Air flow

Balancing section.

The Techgrille

The TECHGRILLE is a round, fully adjustable grille, which

provides superior, quiet air distribution.

4” (100 mm) Part No. 99-EAG4
5” (125 mm) Part No. 99-EAG5
6” (150 mm) Part No. 99-EAG6

The HRV and all condensate lines must be
installed in a space where the temperature is
maintained above the freezing point or freeze
protection must be provided.

CAUTION

DRAIN

SPOUT

ZIP TIE

TO DRAIN

TEE

CONNECTOR

DRAIN

SPOUT

PRE-PUNCHED HOLES (2)

DRAIN PAN

DRAIN PAN

1/2 " I.D.

DRAIN HOSE

DRAIN HOSE PLUMBING

DRAIN

SPOUT

DRAIN

SPOUT

TO DRAIN

1/2" HARD PIPE

TEE

JOINT

PRE-PUNCHED HOLES (2)

DRAIN PAN

DRAIN PAN

HARD PIPE PLUMBING

Drain trap and tubing MUST be below
bottom of door with 1/4" per foot
downwards slope away from unit.

CAUTION

Note: Secondary drain pan may be required to protect from

condensate leakage.

CAUTION

Do not mount exhaust grille within 4’
(1.2m) (horizontally) of a stove to prevent
grease from entering the unit.