3 outputting alarm signals – Furuno FAR-2107(-BB) User Manual

Page 110

Advertising
background image

1. RADAR OPERATION

1-88

[ALARM]

1 BACK
2 GUARD ALARM MODE
IN/OUT
3 GUARD ALARM LEVEL
1/2/3/4
4 WATCH ALARM

OFF/6M/10M/
12M/15/20M

5 ALARM SOUND LEVEL

OFF/LOW/MID/HIGH

6 [ALARM OUT1]
7 [ALARM OUT2]
8 [ALARM OUT3]
9 [ALARM OUT4]
0 [PRIMARY ALARM]

[ALARM

OUT1]


1 BACK
2

TARGET ALARM

WATCH

ALARM

TT

NEW

TARGET

TT

LOST

TARGET

TT

CPA

LIMIT

TT AUTO ACQ TGT FULL
TT

MAN

ACQ

TGT

FULL

TT

SYSTEM

ERROR

AIS

NEW

TARGET

AIS

LOST

TARGET

AIS CPA LIMIT
AIS

TGT

FULL

AZIMUTH
HEAD

LINE

TRIGGER

VIDEO

GYRO LOG EPFS
XTE
ARRIVAL

WPT

DEPTH
ALARM

ACK

OUT

OPERATOR

FITNESS

ANCHOR

WATCH

NO CPA/TCPA FOR AIS
9 ALARM OUT POLARITY
NORMAL/INVERT

1.44.3

Outputting alarm signals

Four ports are provided from which to output alarm signals to external equipment.
Select the port and alarm signals to output as follows:

1. Left-click the MENU box to open the menu.
2. Select 3 [ALARM].









ALARM menu

3. Select appropriate "ALARM OUT" item (6-9).

ALARM OUT1, 2: Normally closed
ALARM OUT3, 4: Normally open

4. Select an alarm to output. The alarm

selected is underlined.

5. Repeat step 5 to select other alarms to

output.

6. Push the right button three times to close the

menu.












ALARM OUT1 menu