Venting installation, Continued – FMI VM36E(B User Manual

Page 10

Advertising
background image

www.fmiproducts.com

108796-01U

10

Maintain

Listed

Clearance

Maintain

Listed

Clearance

12' Min.

12' Min.

45°

45°

6'

8'

12' Min.

60°

45°

Position

Firestop

Position

Firestop

Position

Firestop

Listed

Vent Cap

Listed

Vent Cap

Listed

Vent Cap

Maintain

Listed

Clearance

Maintain

Listed

Clearance

Maintain

Listed

Clearance

Maintain

Listed

Clearance

Support Each

Lateral At

Least Every

6 Feet

Maintain

Listed

Clearance

10'

EXAMPLE 3

EXAMPLE 2

EXAMPLE 1

Figure 10 - Typical B-Vent Configuration

VeNtING INstallatIoN

Continued

If venting horizontally through a side wall be-

comes necessary, a listed thimble approved

for use with B-type vent must be used. Check

with your local codes before venting through

a side wall.
Some codes areas allow the use of existing

B-type vent systems if the system is at or

above the recommended diameter of the flue,

in this case 6".
The flue connection must be made using

listed B-type connectors and the existing

system must be code inspected for damage

and proper installation.
It is not recommended that this appliance be

common vented with an existing gas burning

appliance. However, if it becomes necessary

to common vent this appliance, the venting

system must be sized and configured in ac-

cordance with the common venting guides

Appendix G of the current National Fuel Gas

Code ANSI Z223.1/NFPA 54.
Note: Before connecting this appliance to an

existing vent system or a common venting

system consult with your local architect, plan-

ner or building official.

WARNING: This appliance

must be properly connected

to a system and must not be

connected to a chimney flue

servicing a separate solid fuel

burning appliance.

Lowest

Discharge

Opening

Listed

Vent Cap

8 Ft. Min.

Roof Pitch x/12

Listed Clearance

12

x

Listed

Gas

Vent

H (Min)

Height

From Roof

Figure 11 - B-Vent Terminations

Roof Pitch

H (Min.)

Feet

Meter

Flat to 6/12

1.0

0.30

6/12 to 7/12

1.25

0.38

Over 7/12 to 8/12

1.5

0.46

Over 8/12 to 9/12

2.0

0.61

Over 9/12 to 10/12

2.5

0.76

Over 10/12 to 11/12

3.25

0.99

Over 11/12 to 12/12

4.0

1.22

Over 12/12 to 14/12

5.0

1.52

Over 14/12 to 16/12

6.0

1.83

Over 16/12 to 18/12

7.0

2.13

Over 18/12 to 20/12

7.5

2.27

Over 20/12 to 21/12

8.0

2.44

Advertising